Stall prevention operation (Pr. 22, Pr. 23, Pr. 48, Pr. 66, Pr. 156, Pr. 157)
(1) Block diagram
This function monitors the output current and automatically changes the output frequency to prevent the inverter from
coming to trip due to overcurrent, overvoltage, etc.
It can also limit stall prevention and fast-response current limit operation during acceleration/deceleration, driving or
regeneration.
  Stall prevention
If the output current exceeds the stall prevention operation level, the output frequency of the inverter is
automatically changed to reduce the output current.
Fast-response current limit
If the current exceeds the limit value, the output of the inverter is shut off to prevent an overcurrent.
Parameter 
Number
Name
Initial Value
Setting Range
Description
22
Stall prevention operation 
level
150%
0
Stall prevention operation invalid
0.1 to 200%
Set the current value to start the stall 
prevention operation.
23
Stall prevention 
operation level 
compensation factor 
at double speed
9999
0 to 200%
The stall operation level can be reduced 
when operating at a high speed above the 
rated frequency.
9999
Constant according to Pr. 22.
48
Second stall prevention 
operation current
9999
0
Stall prevention operation invalid
0.1 to 200%
Second stall prevention operation level
9999
Same level as Pr. 22.
66
Stall prevention 
operation reduction 
starting frequency
60Hz
0 to 400Hz
Set the frequency at which the stall 
operation level is started to reduce.
156
Stall prevention operation 
selection
0
0 to 31, 100, 101
Select whether stall prevention operation 
and fast-response current limit operation 
will be performed or not.
157
OL signal output timer
0s
0 to 25s
Output start time of the OL signal output 
when stall prevention is activated.
9999
Without the OL signal output
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
Stall prevention operation level
Stall prevention operation invalid
RT
= 0
-
+
Pr. 48
Pr. 22
Output frequency
Pr. 23Pr. 66
RT
    0