93
Frequency setting by external terminals
4.6.3
Remote setting function (Pr. 59)
The above parameter can be set when Pr. 160 Extended function display selection = "0". (Refer to page 156)
* External running frequency (other than multi-speed) or PU running frequency 
NOTE
When Pr. 29 Acceleration/deceleration pattern selection =  "1"  (S-pattern acceleration/deceleration A), the acceleration/
deceleration time is the period of time required to reach Pr. 3 Base frequency. 
The Pr. 15 setting should be equal to or higher than the Pr. 13 Starting frequency.  
The JOG signal can be assigned to the input terminal using any of Pr. 178 to Pr. 182 (input terminal function selection).
When terminal assignment is changed, the other functions may be affected. Please make setting after confirming the
function of each terminal.
During Jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second
functions are valid. (Refer to page 227))
When Pr. 79 Operation mode selection = "4", pressing 
 of the operation panel and 
/
 
of the parameter unit
(FR-PU04/FR-PU07) starts the inverter and pressing 
 stops the inverter.
This function is invalid when Pr. 79 = "3".
Parameters referred to
Pr. 13 Starting frequency 
 
Pr. 29 Acceleration/deceleration pattern selection 
Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments 
 
Pr. 79 Operation mode selection 
Pr. 178 to Pr. 182 (input terminal function selection)
 
Even if the operation panel is located away from the enclosure, you can use contact signals to perform continuous
variable-speed operation, without using analog signals.
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
RH, RM, RL signal 
function
Frequency setting
storage function
59
Remote function selection
0
0
Multi-speed setting
1
Remote setting
With
2
Remote setting
Not used
3
Remote setting
Not used
(Turning STF/STR off 
clears remotely-set 
frequency.)
Forward rotation
Acceleration
Deceleration
Clear
Inverter
Connection diagram 
for remote setting
STF
RH
RM
RL
SD
10
2
5
0
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Deceleration
 (RM)
Clear (RL)
Acceleration
 (RH)
Forward rotation
 (STF)
Power supply
0Hz
Time
Output frequency (Hz)
*
When 
Pr. 59 = 1
When 
Pr. 59 = 2, 3
When 
Pr. 59 = 1, 2
When 
Pr. 59 = 3