4.12.4 Shortest acceleration/deceleration and optimum acceleration/deceleration 
(automatic acceleration/deceleration) (Pr. 61 to Pr. 63, Pr. 292, Pr. 293)
(1) Shortest acceleration/deceleration mode (Pr. 292 = "1, 11", Pr. 293)
⋅ Set when you want to accelerate/decelerate the motor for the shortest time. It is desired to make acceleration/
deceleration in a shorter time for a machine tool etc. but the design values of machine constants are unknown.
⋅ Acceleration/deceleration speed is automatically adjusted at a start of acceleration/deceleration so that
acceleration/deceleration is made with the maximum torque the inverter can output according to the setting value
of Pr. 7 Acceleration time and Pr. 8 Deceleration time. (The setting values of Pr. 7 and Pr. 8 are not changed)
⋅ Either acceleration or deceleration can be made in the shortest time using Pr. 293 Acceleration/deceleration separate
selection
When the setting value is "0" (initial value), both acceleration and deceleration can be made in the shortest time.
⋅ Since the 7.5K or lower inverter has a built-in brake resistor, set Pr. 292 to "11". Set "11" also when a high-duty
brake resistor or brake unit is connected. Deceleration time can be further shortened.
⋅ When the shortest acceleration/deceleration mode is selected under V/F control and Advanced magnetic flux
vector control, the stall prevention operation level during acceleration/deceleration becomes 150% (adjustable
using Pr. 61 to Pr. 63 ). The setting of Pr. 22 Stall prevention operation level and stall level by analog input are used
only during a constant speed operation.
Adjustment using Pr. 61 to Pr. 63 cannot be made under Real sensorless vector control or vector control since
torque limit level (Pr. 22 etc.) is used during acceleration/deceleration.
⋅ It is inappropriate to use for the following applications.
a)Machine with a large inertia such as a fan (more than 10 times). Since stall prevention operation will be
activated for a long time, this type of machine may trip due to motor overloading, etc. 
b)It is desired to always perform operation with a constant acceleration/deceleration time.
The inverter operates in the same conditions as when appropriate values are set in each parameter even if
acceleration/deceleration time and V/F pattern are not set. This function is useful when you just want to operate,
etc. without fine parameter setting.
Parameter 
Number
Name
Initial 
Value
Setting Range
Description
61
Reference current
9999
55K or 
lower
0 to 500A
Set the reference current during shortest/ optimum 
acceleration/deceleration.
75K or 
higher
0 to 3600A
9999
Rated inverter output current value is reference
62
Reference value 
at acceleration
9999
0 to 220%
Set the limit value/optimum value during shortest/
optimum acceleration.
9999
Shortest acceleration/deceleration: 150% is a limit value
Optimum acceleration/deceleration: 100% is an 
optimum value
63
Reference value 
at deceleration
9999
0 to 220%
Set the limit value/optimum value during shortest/
optimum deceleration.
9999
Shortest acceleration/deceleration: 150% is a limit value
Optimum acceleration/deceleration: 100% is an 
optimum value
292
Automatic 
acceleration/
deceleration
0
0
Normal operation mode
1
Shortest acceleration/deceleration mode (without 
brake)
11
Shortest acceleration/deceleration mode (with brake)
3
Optimum acceleration/deceleration mode
5, 6
Elevator mode1, 2 (Refer to page 163
7, 8
Brake sequence mode 1, 2 (Refer to page 217.)
293
Acceleration/
deceleration 
separate 
selection
0
0
Both acceleration and deceleration are made in the 
shortest/optimum acceleration/deceleration mode
1
Only acceleration is made in the shortest/optimum 
acceleration/deceleration mode
2
Only deceleration is made in the shortest/optimum 
acceleration/deceleration mode
REMARKS
⋅ Even if automatic acceleration/deceleration mode has been selected, inputting the JOG signal (Jog operation), RT signal
(second function selection) or X9 signal (third function selection) during an inverter stop will switch to the normal operation and
give priority to jog operation, second function selection or third function selection. Note that JOG and RT signal input is invalid
even if JOG signal and RT signal are input during operation in automatic acceleration/deceleration mode.
⋅ Since acceleration/deceleration is made with the stall prevention operation being activated, the acceleration/deceleration speed
always varies according to the load conditions.
⋅ Note that when proper values are set in Pr. 7 and Pr. 8 , acceleration/deceleration time may be shorter than selecting shortest
acceleration/deceleration mode.