Motor brake and stop operation
4.14.4 Stop-on contact control function (Pr. 6, Pr. 48, Pr. 270, Pr. 275, Pr. 276) 
*1
This parameter allows its setting to be changed during operation in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write
selection
.
*2
This parameter allows its setting to be changed during operation even if "0" (initial value) is set in Pr. 77 Parameter write selection.
.............Specifications differ according to the date assembled. Refer to page 484  to check the SERIAL number.
<Connection and operation example>
To ensure accurate positioning at the upper limit etc. of
a lift, stop-on-contact control causes a mechanical
brake to be closed while the motor is developing a
holding torque to keep the load in contact with a
mechanical stopper etc.
This function suppresses vibration which is liable to
occur when the load is stopped upon contact in vertical
motion applications, ensuring steady precise
positioning.
Parameter 
Number
Name
Initial 
Value
Setting Range
Description
6
Multi-speed setting 
(low speed)
10Hz
0 to 400Hz
Set the output frequency for stop-on-contact control.
Stall prevention 
operation level
150%
0 to 400%
Set the stall prevention operation level for stop-on-contact 
control.
The smaller value set in either Pr. 22 or Pr. 48 has a priority.
48
Second stall 
prevention 
operation current
150%
0 to 220%
270
Stop-on contact/
load torque high-
speed frequency 
control selection
0
0
Normal operation
1
Stop-on-contact control
2
Load torque high speed frequency control (Refer to page 374) 
3
Stop-on-contact+load torque high speed frequency control 
(Refer to page 374
11
Stop-on-contact control
E.OLT invalid under 
stop-on-contact 
control
13
Stop-on-contact+load torque high speed 
frequency control (Refer to page 374)
275 
Stop-on contact 
excitation current 
low-speed 
multiplying factor
9999
0 to 1000%
Set the force (holding torque) for stop-on-contact control.
Normally set 130% to 180%.
9999
No compensation.
276
PWM carrier 
frequency at stop-
on contact
9999
55K or lower
0 to 9 Set a PWM carrier frequency for stop-on-contact control.
For Real sensorless vector control, carrier frequency is 
always 2Hz when a setting value is 0 to 5 and always 6Hz 
when a setting value is 6 to 9. (Valid at the frequency of 3Hz 
or less.)
75K  or higher 0 to 4
9999
As set in Pr. 72 PWM frequency selection .
Magnetic flux
Magnetic flux
Magnetic flux
Sensorless
Sensorless
Sensorless
<Without stop-on-contact control>
Vibration
Complete stop
Lift
Lift
<With stop-on-contact control>
Power 
supply
Forward rotation command
High-speed operation command
Middle-speed operation command
Stop-on contact selection 0
Stop-on contact selection 1
MCCB
R/L1
S/L2
T/L3
STF
RH *
RM *
RL *
RT *
U
V
W
MC
Mechanical
brake
Motor
* The input terminal used differs according to the Pr. 180 to Pr. 189 settings.
SD
Sink logic
(a)
(b)
(c)
Time
Pr. 4
RH
RM
RL
RT
Pr. 5
Pr. 6
Output frequency
0
Normal mode Stop-on contact 
control mode
(a):Acceleration time (Pr. 7 )
(b):Deceleration time (Pr. 8 )
(c):Second deceleration time (Pr. 44/Pr. 45 )
*
ON
OFF
ON
OFF
ON
OFF
ON
Goes into stop-on-contact control mode when 
both RL and RT switch on.
*RL and RT may be switched on in any order
 with any time difference