334
Communication operation and setting
[RS-485 terminal communication related parameter]
4.24.4 Communication EEPROM write selection (Pr. 342)
⋅ When changing the parameter values frequently, set "1" in Pr. 342 to write them to the RAM. The life of the EEPROM will
be shorter if parameter write is performed frequently with the setting unchanged from "0 (initial value)" (EEPROM write).
Parameter 
Number
Name
Initial 
Value
Setting Range
Description
331
RS-485 communication station 
number
0
0 to 31 (0 to 247) 
*1 *5
Set the inverter station number. (same 
specifications as Pr. 117)
332
RS-485 communication speed
96
3, 6, 12, 24, 48, 
96, 192, 384
Used to select the communication speed. 
(same specifications as Pr. 118)
333 
*2
RS-485 communication stop bit 
length
1
 0, 1, 10, 11
Select stop bit length and data length. (same 
specifications as Pr. 119)
334
RS-485 communication parity 
check selection
2
 
0,  1,  2
Select the parity check specifications. (same
specifications as Pr. 120)
335 
*3
RS-485 communication retry 
count
1
 0 to 10,  9999
Set the permissible number of retries at
occurrence of a data receive error. 
(same specifications as Pr. 121)
336 
*3
RS-485 communication check 
time interval
0s
0
RS-485 communication can be made, but the
inverter trips in the NET operation mode.
 0.1 to 999.8s
Set the interval of communication check 
(signal loss detection) time. (same 
specifications as Pr. 122)
9999
No communication check (signal loss 
detection)
337 
*3
RS-485 communication waiting 
time setting
9999
 0 to 150ms,  
9999
Set the waiting time between data 
transmission to the inverter and response. 
(same specifications as Pr. 123)
341 
*3
RS-485 communication CR/LF 
selection
1
 
0,  1,  2
Select presence/absence of CR/LF. 
(same specifications as Pr. 124)
549
Protocol selection
0
0
Mitsubishi inverter (computer link) protocol
1
Modbus-RTU protocol 
*4
*1
When "1" (Modbus-RTU protocol) is set in Pr. 549, the setting range within parentheses is applied.
*2
For the Modbus-RTU protocol, the data length is fixed to 8 bits and the stop bit depends on the Pr. 334 setting. (Refer to page 347)
*3
Invalid during the Modbus-RTU protocol.
*4
The Modbus-RTU protocol is valid for only communication from the RS-485 terminals.
*5
The inverter works with the initial value if a value other than the setting range is set.
CAUTION
⋅ If communication is made without Pr. 336 RS-485 communication check time interval being changed from "0" (initial value), monitor,
parameter read, etc. can be performed, but the inverter results in a fault as soon as it is switched to the NET operation mode. If
the operation mode at power ON is the Network operation mode, a communication fault (E.SER) occurs after first
communication. 
When performing operation or parameter write through communication, set "9999" or a greater value to Pr. 336. (The setting
depends on the computer side program.) (Refer to page 339)
⋅ Always reset the inverter after making the initial settings of the parameters. After you have changed the communication-related
parameters, communication cannot be made until the inverter is reset.
When parameter write is performed from PU connector, RS-485 terminal, USB communication, and
communication option connected to the inverter, parameter’s storage device can be changed from EEPROM +
RAM to only RAM. Set this parameter when frequent parameter changes are required.
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
342
Communication EEPROM write 
selection
0
0
Parameter values written by communication
are written to the EEPROM and RAM.
1
Parameter values written by communication
are written to the RAM.
The above parameters 
can be set any time when the communication option is connected.
 (Refer to page 308)
REMARKS
⋅ When Pr. 342 
is set to 
"1" (only RAM write)
, the new values of the parameters will be cleared at power supply-off of the inverter.
Therefore, the parameter values available when power is switched ON again are the values stored in EEPROM previously.