Special operation and frequency control
(1) PID control basic configuration
⋅ Pr. 128 = "10, 11" (Deviation value signal input)
*
Set  0  in  Pr. 868 Terminal 1 function assignment. PID control is invalid when Pr. 868
 ≠ 0.
⋅ Pr. 128 = "20, 21" (Measured value input)
*1 Note that terminal 1 input is added to the set point of terminal 2 input. 
*2 Set 0 in Pr. 858 Terminal 4 function assignment. PID control is invalid when Pr. 858
 ≠ 0
134 
PID differential time
9999
0.01 to 
10.00s
For deviation lamp input, time (Td) required for providing only 
the manipulated variable for the proportional (P) action. As the 
differential time increases, greater response is made to a 
deviation change.
9999
No differential control
575
Output interruption 
detection time
1s
 0 to 3600s
The inverter stops operation if the output frequency after PID 
operation remains at less than the Pr. 576 setting for longer 
than the time set in Pr. 575.
9999
Without output interruption function
576
Output interruption 
detection level
0Hz
 0 to 400Hz
Set the frequency at which the output interruption processing 
is performed.
577
Output interruption 
cancel level
1000% 900 to 1100%
Set the level (Pr. 577 minus 1000%) at which the PID output 
interruption function is canceled.
*1
Pr. 129, Pr. 130, Pr. 133 and Pr. 134 can be set during operation. They can also be set independently of the operation mode.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
+-
M
Deviation signal
Feedback signal (measured value)
Ti   S 
1
1+
+Td   S
Kp
PID operation
To outside
Set point
Inverter circuit                 
Motor
Terminal 1
0 to    10VDC
(0 to     5V)
Kp: Proportionality constant   Ti: Integral time   S: Operator   Td: Differential time
Manipulated 
variable
*
+-
M
Ti
S
Kp 1+             +Td    S
1
PID operation
Pr. 133 or 
terminal 2
Set point
Inverter circuit
Motor
Feedback signal (measured value)
Terminal 4
Kp: Proportionality constant   Ti: Integral time   S: Operator   Td: Differential time
Manipulated 
variable
0 to 5VDC
(0 to 10V, 4 to 20mA)
4 to 20mADC (0 to 5V, 0 to 10V)
*1
*2