Check first when you have a trouble
5.5.5
Motor rotates in the opposite direction
5.5.6
Speed greatly differs from the setting
5.5.7
Acceleration/deceleration is not smooth
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Main 
Circuit
Phase sequence of output terminals U, V and W is 
incorrect.
Connect phase sequence of the output cables (terminal 
U, V, W) to the motor correctly.
Input 
signal
The start signals (forward rotation, reverse rotation) are 
connected improperly.
Check the wiring. (STF: forward rotation , STR: reverse 
rotation)
The polarity of the frequency command is negative 
during the polarity reversible operation set by Pr. 73 
Analog input selection
.
Check the polarity of the frequency command.
Input 
signal
Parameter 
setting
Torque command is negative during torque control 
under vector control. 
Check the torque command value.
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Input 
signal
Frequency setting signal is incorrectly input.
Measure the input signal level.
The input signal lines are affected by external EMI.
Take countermeasures against EMI such as using 
shielded wires for input signal lines.
Parameter 
Setting
Pr. 1, Pr. 2, Pr. 18, calibration parameter C2 to C7 settings 
are improper.
Check the settings of Pr. 1 Maximum frequency, Pr. 2 
Minimum frequency, Pr. 18 High speed maximum frequency.
Check the calibration parameter C2 to C7 settings.
Pr. 31 to Pr. 36 (frequency jump) settings are improper.
Narrow down the range of frequency jump.
Load 
Stall prevention (torque limit) function is activated due to 
a heavy load.
Reduce the load weight.
Parameter 
Setting
Set Pr. 22 Stall prevention operation level  (Torque limit level) 
higher according to the load. (Setting Pr. 22 too large 
may result in frequent overcurrent trip (E.OC ).)
Motor
Check the capacities of the inverter and the motor.
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Parameter 
Setting
Acceleration/deceleration time is too short.
Increase acceleration/deceleration time.
Torque boost (Pr. 0, Pr. 46Pr. 112) setting is improper 
under V/F control, so the stall prevention function is 
activated. 
Increase/decrease Pr. 0 Torque boost setting value by 
0.5% increments to the setting. Deactivate stall 
prevention.
The base frequency setting and the motor characteristic 
does not match. 
For V/F control, set Pr. 3 Base frequencyPr. 47 Second V/F 
(base frequency)
, and Pr.113 Third V/F (base frequency)
For vector control, set Pr.84 Rated motor frequency.
Regeneration avoidance operation is performed
If the frequency becomes unstable during regeneration 
avoidance operation, decrease the setting of Pr. 886 
Regeneration avoidance voltage gain
.
Load 
Stall prevention (torque limit) function is activated due to 
a heavy load.
Reduce the load weight.
Parameter 
Setting
Set Pr. 22 Stall prevention operation level  (Torque limit level) 
higher according to the load. (Setting Pr. 22 too large 
may result in frequent overcurrent trip (E.OC ).)
152 
Motor
Check the capacities of the inverter and the motor.