Applied motor (Pr. 71)
(1) Set the motor to be used
Refer to the following list and set this parameter according to the motor used.
Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is necessary when using a constant-torque motor. Thermal characteristic of the electronic
thermal relay function suitable for the motor is set.
When PM sensorless vector control is selected, the motor constants (MM-CF etc.) necessary for control
are selected as well.
Parameter 
Number
Name
Initial 
Value
Setting Range
Description
71
Applied motor
0
0 to 8, 13 to 18, 20, 23, 
24, 30, 33, 34, 40, 43, 
44, 50, 53, 54, 330, 333, 
334, 8093, 8094
Selecting the standard motor or constant-
torque motor sets the corresponding 
motor thermal characteristic.
Pr. 71 Setting
Motor
Electronic thermal relay 
function operation 
characteristic
Constant 
torque
IPM
330
*
IPM Motor MM-CF
333
*
IPM Motor MM-CF
Select "offline auto tuning setting"
8093
IPM Motor (other than MM-CF)
334
*
IPM Motor MM-CF
Auto tuning data can be read, 
changed, and set
8094
IPM Motor (other than MM-CF)
* The setting is available for FR-A720-11K or lower.
REMARKS
 When performing offline auto tuning, set "3, 7, 8, 13, 17, 18, 23, 33, 43, 53, 333, 8093" in Pr. 71.
(Refer to page 7 for offline auto tuning)
 For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically
changed according to the Pr. 71 setting as follows.
Pr.71
Standard Motor Setting
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44,
330, 333, 334, 8093, 8094
Constant Torque 
Motor Setting
1, 13 to 18, 50, 53, 54
Pr. 0
3%
2%
Pr. 12
4%
2%