EMC and leakage currents
1) Calculation of equivalent capacity P0 of harmonic generating equipment
The "equivalent capacity" is the capacity of a 6-pulse converter converted from the capacity of consumer's harmonic
generating equipment and is calculated with the following equation. If the sum of equivalent capacities is higher than
the limit in Table 3, harmonics must be calculated with the following procedure:
2) Calculation of outgoing harmonic current
Outgoing harmonic current = fundamental wave current (value converted from received power voltage) 
× operation
ratio 
× harmonic content
⋅Operation ratio: Operation ratio = actual load factor × operation time ratio during 30 minutes
⋅Harmonic content: Found in Table 4.
P0 = 
Σ (Ki × Pi) [kVA]
* Rated capacity: Determined by the capacity of the applied motor and
found in Table 5. It should be noted that the rated capacity used here
is used to calculate generated harmonic amount and is different from
the power supply capacity required for actual inverter drive.
Ki: Conversion factor(According to Table 2)
Pi: Rated capacity of harmonic generating equipment
*
 [kVA]
i : Number indicating the conversion circuit type
Table 5 Rated capacities and outgoing harmonic currents of inverter-driven motors
Applied
Motor 
(kW)
Rated Current 
(A)
Fundamental 
Wave Current 
Converted 
from 6.6kV 
(mA)
Rated 
Capacity 
(kVA)
Outgoing Harmonic Current Converted from 6.6kV (mA)
(No reactor, 100% operation ratio)
200V
400V
5th
7th
11th
13th
17th
19th
23rd
25th
0.4
1.61
0.81
49
0.57
31.85
20.09
4.165
3.773
2.107
1.519
1.274
0.882
0.75
2.74
1.37
83
0.97
53.95
34.03
7.055
6.391
3.569
2.573
2.158
1.494
1.5
5.5
2.75
167
1.95
108.6
68.47
14.20
12.86
7.181
5.177
4.342
3.006
2.2
7.93
3.96
240
2.81
156.0
98.40
20.40
18.48
10.32
7.440
6.240
4.320
3.7
13.0
6.50
394
4.61
257.1
161.5
33.49
30.34
16.94
12.21
10.24
7.092
5.5
19.1
9.55
579
6.77
376.1
237.4
49.22
44.58
24.90
17.95
15.05
10.42
7.5
25.6
12.8
776
9.07
504.4
318.2
65.96
59.75
33.37
24.06
20.18
13.97
11
36.9
18.5
1121
13.1
728.7
459.6
95.29
86.32
48.20
34.75
29.15
20.18
15
49.8
24.9
1509
17.6
980.9
618.7
128.3
116.2
64.89
46.78
39.24
27.16
18.5
61.4
30.7
1860
21.8
1209
762.6
158.1
143.2
79.98
57.66
48.36
33.48
22
73.1
36.6
2220
25.9
1443
910.2
188.7
170.9
95.46
68.82
57.72
39.96
30
98.0
49.0
2970
34.7
1931
1218
252.5
228.7
127.7
92.07
77.22
53.46
37
121
60.4
3660
42.8
2379
1501
311.1
281.8
157.4
113.5
95.16
65.88
45
147
73.5
4450
52.1
2893
1825
378.3
342.7
191.4
138.0
115.7
80.10
55
180
89.9
5450
63.7
3543
2235
463.3
419.7
234.4
169.0
141.7
98.10
Applied
Motor 
(kW)
Rated Current 
(A)
Fundamental 
Wave Current 
Converted 
from 6.6kV 
(mA)
Rated 
Capacity 
(kVA)
Outgoing Harmonic Current Converted from 6.6kV (mA)
(With DC reactor, 100% operation ratio)
200V
400V
5th
7th
11th
13th
17th
19th
23rd
25th
75
245
123
7455
87.2
2237
969
626
373
350
239
224
164
90
293
147
8909
104
2673
1158
748
445
419
285
267
196
110
357
179
10848
127
3254
1410
911
542
510
347
325
239
132
216
13091
153
3927
1702
1100
655
615
419
393
288
160
258
15636
183
4691
2033
1313
782
735
500
469
344
220
355
21515
252
6455
2797
1807
1076
1011
688
645
473
250
403
24424
286
7327
3175
2052
1221
1148
782
733
537
280
450
27273
319
8182
3545
2291
1364
1282
873
818
600
315
506
30667
359
9200
3987
2576
1533
1441
981
920
675
355
571
34606
405
10382
4499
2907
1730
1627
1107
1038
761
400
643
38970
456
11691
5066
3274
1949
1832
1247
1169
857
450
723
43818
512
13146
5696
3681
2191
2060
1402
1315
964
500
804
48727
570
14618
6335
4093
2436
2290
1559
1462
1072