201
*1
These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485 communication.
(Refer to 
Chapter 4 of 
 the Instruction Manual (Applied)
 for RS-485 communication)
*2
Validity and invalidity according to operation mode are as follows:
{
:Usable parameter
×
:Unusable parameter
Δ :Parameters available only during position control set by parameter
*3
"{" indicates valid and "
×" indicates invalid of "parameter copy", "parameter clear", and "all parameter clear". 
*4
Parameters can be used with conditions. Refer to 
Chapter 4 of 
 the Instruction Manual (Applied)
 for details.
*5
When a communication option is installed, parameter clear (lock release) during password lock (Pr. 297 
≠ 9999) can be performed only from the
communication option.
*6
These parameters are communication parameters that are not cleared when parameter clear (all clear) is executed from RS-485 communication.
(Refer to 
Chapter 4 of 
 the Instruction Manual (Applied)
 for RS-485 communication)
Symbols in the table indicate parameters which function when an option is mounted.
........ FR-A7AX, ......... FR-A7AY,  ......... FR-A7AR,  ........ FR-A7AP,  ......... FR-A7AL, ......... FR-A7AZ, 
........ FR-A7NC,
......... FR-A7ND, ........ FR-A7NL, ......... FR-A7NP, ......... FR-A7NS
Appendix 4 Control mode-based parameter  (function) correspondence 
table and instruction code list
Param
eter
Name
Instruction 
Code
 * 1
Control Mode-based Correspondence Table
 *2
P
aram
et
er Co
p
y
  *
3
Par
amet
er Cl
ear 
*3
A
ll Param
et
er
 Cl
ea
*3
Re
a
d
Wr
it
e
Exten
ded
V/F
Control
Advanced
magnetic 
flux
vector 
control
Vector control
Real sensorless 
vector control
Speed
control
Torque
control
Position
control
S
p
eed
contr
o
l
To
rque
contr
o
l
 0
Torque boost
00
80
0
{
×
×
×
×
×
×
{
{
{
 1
Maximum frequency
01
81
0
{
{
{
{
{
{
{
{
{
{
 2
Minimum frequency
02
82
0
{
{
{
{
×
{
{
{
{
{
 3
Base frequency
03
83
0
{
×
×
×
×
×
×
{
{
{
 4
Multi-speed setting (high speed)
04
84
0
{
{
{
{
Δ
{
{
{
{
{
 5
Multi-speed setting (middle speed)
05
85
0
{
{
{
{
Δ
{
{
{
{
{
 6
Multi-speed setting (low speed)
06
86
0
{
{
{
{
Δ
{
{
{
{
{
 7
Acceleration time
07
87
0
{
{
{
{
Δ
{
{
{
{
{
 8
Deceleration time
08
88
0
{
{
{
{
Δ
{
{
{
{
{
 9
Electronic thermal O/L relay
09
89
0
{
{
{
{
{
{
{
{
{
{
10
DC injection brake operation 
frequency
0A
8A
0
{
{
{
{
×
{
{
{
{
{
11
DC injection brake operation 
time
0B
8B
0
{
{
{
{
×
{
{
{
{
{
12
DC injection brake operation 
voltage
0C
8C
0
{
{
×
×
×
{
*4
{
*4
{
{
{
13
Starting frequency
0D
8D
0
{
{
{
{
×
{
{
{
{
{
14
Load pattern selection
0E
8E
0
{
×
×
×
×
×
×
{
{
{
15
Jog frequency
0F
8F
0
{
{
{
{
×
{
{
{
{
{
16
Jog acceleration/
deceleration time
10
90
0
{
{
{
{
×
{
{
{
{
{
17
MRS input selection
11
91
0
{
{
{
{
{
{
{
{
{
{
18
High speed maximum 
frequency
12
92
0
{
{
×
×
×
×
×
{
{
{
19
Base frequency voltage
13
93
0
{
×
×
×
×
×
×
{
{
{
20
Acceleration/deceleration 
reference frequency
14
94
0
{
{
{
{
Δ
{
{
{
{
{
21
Acceleration/deceleration 
time increments
15
95
0
{
{
{
{
Δ
{
{
{
{
{
22
Stall prevention operation 
level (Torque limit level )
16
96
0
{
{
{
×
{
{
×
{
{
{
23
Stall prevention operation 
level compensation factor at 
double speed
17
97
0
{
{
×
×
×
×
×
{
{
{
24
Multi-speed setting (speed 4)
18
98
0
{
{
{
{
Δ
{
{
{
{
{
25
Multi-speed setting (speed 5)
19
99
0
{
{
{
{
Δ
{
{
{
{
{