25
Basic operation (Speed setting, run,
speed meter adjustment)
3.2.2
Adjustment (calibration) of speed meter (meter)
At the preset speed of 1500r/min, make adjustment so that the meter (analog meter)
deflects to full-scale. Calibrate the DA1 terminal (±10V).(in PU operation mode)
POINT
• Pr. 900 "DA1 terminal calibration" can be read by setting "1" (extended function parameter enable) in
Pr. 160 "extended function selection".
• Set Pr. 900 "DA1 terminal calibration".
• Set any of "1 to 3, 5 to 12, 17, 18, 21, 32 to 34 and 36" in Pr. 54 "DA1 terminal function selection" to
output a signal to the terminal DA1. (Refer to page 56)
CAUTION
1. When the speed meter is connected across terminals DA1-5 to monitor the speed, the output of ter-
minal DA1 is saturated if the maximum output speed reaches or exceeds 1500r/min, with the factory
setting unchanged. Hence, the setting of Pr. 55 "speed monitoring reference" must be changed to the
maximum output speed. (Refer to page 56.)
2. Terminal DA2 can be adjusted in Pr. 901
3. For operation from the parameter unit (FR-PU04V), refer to the instruction manual of the FR-PU04V. 
REMARKS
• For monitor display changes by 
, refer to page 
• Calibration can be made also during external operation.
Changing example
1.
3.
4.
2.
MODE
MODE
FWD
FR-DU04
-1
CONTROL PANEL
Hz¤r
MON
EXT
PU
A
V
REV
FWD
5.
6.
SET
REV
Operation
Press        to select the parameter setting mode.
Display the present operation speed by pressing            to
read Pr. 900.
Flicker ... 
Parameter setting complete!!
Press         to operate the inverter. (It is not necessary to 
connect a motor.)
Press       or        to adjust the meter pointer to 
a predetermined position. (Depending on the setting, 
it may take some time until the pointer moves.)
Press         for about 1.5s.
This completes the setting.
REMARKS
1. Pressing         to start reverse rotation operation will move the meter pointer 
    reversely (in the negative direction).
2. The terminal DA1 output will also keep displaying the monitor when the 
    inverter stops due to an alarm.
Display
(Analog voltage meter)
Press                    to stop the inverter.
STOP
RESET
SET
SET
MODE