Easy gain tuning
4.5.5
Easy gain tuning-related parameter operation
R efe r to th e follow ing ta ble for the p aram eter/g ain re ad/w rite o pera tio n using  P r. 8 19 "ea sy gain tu ning selection ".
Pr. 819=0
Without tuning
Pr. 819=1
With inertia estimation, with gain 
calculation
Pr. 819=2
Inertia as set in Pr. 880, with gain 
calculation
Pr. 880
"load inertia"
Read
Setting is 
displayed.
Inertia estimation result is 
displayed from the RAM.
Setting is displayed.
Write
Setting can be 
changed.
Load inertia estimation result is 
written. (Write is enabled only 
during a stop.)
Setting can be changed.
Timing of writing load 
inertia ratio and control 
gains into E
2
PROM
Not written
•Every hour after power-on
•When the Pr. 819 setting is 
changed to other than "1".
•When the vector control mode is 
changed to other drive systems 
due to the Pr. 800 "control system 
selection" setting change.
When the Pr. 819 setting is 
changed to "2"
When Pr. 880 "load ineritia ratio" or 
Pr. 818 "easy gain tuning response 
level setting" is changed
Control gains
(Pr. 820, Pr. 821, 
Pr. 828, Pr. 422)
Read
Settings are 
displayed.
Gain calculation results (RAM) are 
displayed.
Settings are displayed.
Write
Settings can be 
changed.
Write disabled (operation error)
Write disabled (operation error)
CAUTION
RAM data is erased when the power is not supplied or the inverter is reset.