Справочник Пользователя для Mitsubishi Electronics FR-V500

Скачать
Страница из 112
89
Troubleshooting
6.4.6
Speed command does not match motor speed
(1) Speed control
Y
N
Y
N
N
Y
Y
N
Y
N
The speed command does
not match the motor speed.
Have you set the
motor type?
Does the speed command
from the command device
match the motor speed?
Does the speed command
match the inverter's speed
command?
Does the speed remain
unchanged if it is
increased?
Set the motor (Pr. 71).
1) Check that the command device
    is not faulty.
2) The command is compounded with
    noise (check the shielding and wiring.)
Does the inverter's speed
command match the motor
speed?
Set the speed command
bias and gain
(Pr. 902, Pr. 903).
1) Torque is insufficient.
    Increase the torque restriction
    value as the torque restriction
    value is exceeded.
2) Check that the speed control
    proportional gain (Pr. 820)
    is not 0.
3) Increase the motor and
    inverter capacities as they
    are insufficient.
Y
Is the PLG setting
 correct?
Make the PLG setting 
correctly.
The number of PLG pulses
(Pr. 851) is wrong.
Set the number of PLG
pulses.
N
Please contact your sales 
representative.