Справочник Пользователя для Mitsubishi Electronics FR-V540-1.5K to 55K

Скачать
Страница из 232
97
Display functions 1 (Pr. 52 to Pr. 56)
P
A
RAMETERS
3
3.7 Display functions 1 (Pr. 52 to Pr. 56)
3.7.1
Monitor display/DA1, DA2 terminal function selection 
 
(Pr. 52 to Pr. 54, Pr. 158
)
<Setting>
Any of the following signals can be monitored by parameter setting.
The signals marked 
× cannot be selected for monitoring.
During operation, you can select the signals shown on the control panel (FR-DU04
-1
)/parameter unit (FR-
PU04V) main display screen and on the parameter unit (FR-PU04V) level meter and the signals output to the 
DA1 and DA2 terminals.
• There are two analog output DA1 and DA2 terminals.
 
Select the signals using Pr. 54 and Pr. 158.
Parameter
Name
Factory 
Setting
Setting Range
Remarks
52
DU/PU main display data 
selection
0
0, 5 to 12, 17 to 20, 23, 24, 
32 to 35, 38, 100
(5 to 12 are invalid for FR-PU04V)
Extended mode
53
PU level display data 
selection
1
0 to 3, 5 to 12, 17, 18
54
DA1 terminal function 
selection
1
1 to 3, 5 to 12, 17, 18, 21, 
32 to 34, 36
158
DA2 terminal function 
selection
1
1 to 3, 5 to 12, 17, 18, 21, 
32 to 34, 36
Signal 
Type
Display
 Unit
Parameter Settings
± Output
Full-Scale Value 
of the Level 
Meter Connected 
to DA1 and DA2
Description
Pr. 52
Pr. 53 Pr. 54 Pr. 158
DU LED
PU main 
monitor
PU level 
meter
DA1
 terminal
12 bits
(±10V)
DA2
 terminal
12 bits
(+10V)
No display
——
×
×
0
×
——
When "0" is set in Pr. 53, the level 
meter of the parameter unit is not 
displayed.
Speed
0.1
r/min
0/100
0/100
1
1
Pr. 55
Output 
current
0.01A 0/100
0/100
2
2
×
Pr. 56
The output current is displayed as 
effective value.
Output 
voltage
0.1V
0/100
0/100
3
3
×
400V/800V
The output voltage is displayed as 
effective value.
Alarm 
display
——
0/100
0/100
×
×
×
——
————
Set speed
0.1
r/min
5
*2
5
5
×
Pr. 55
Under speed control, the current 
speed setting is displayed.
0r/min under position control.
Output 
frequency
0.01
Hz
6
*2
6
6
The frequency 
converted from Pr. 
55
The output frequency is displayed.
Motor 
torque
0.1%
7
*2
7
7
Pr. 866
The output torque is displayed. The 
ratio to the rated torque is displayed.
When the DA1 output monitor is 
used, a positive voltage is output 
during forward driving and reverse 
regeneration and a negative 
voltage is output during reverse 
driving and forward regeneration.
Converter 
output 
voltage
0.1V
8
*2
8
8
×
400V/800V
DC bus voltage is displayed.
speed
torque
position