Control circuit terminal specifications
1.4.1
Connecting the control circuit to a power supply separately from the main circuit
If the magnetic contactor (MC) in the inverter power supply is opened when the protective circuit is operated, the 
inverter control circuit power is lost and the alarm output signal cannot be kept on. To keep the alarm signal on 
terminals R1 and S1 are available. In this case, connect the power supply terminals R1 and S1 of the control circuit 
to the primary side of the MC.
 Model FR-V520-1.5K, 2.2K, FR-V540-1.5K, 2.2K
<Connection procedure>
 Model FR-V520-3.7K to 55K, FR-V540-3.7K to 55K
<Connection procedure>
CAUTION
1. When the main circuit power (R, S, T) is on, do not switch off the control power (terminals R1, S1). 
Otherwise the inverter may be damaged.
2. When using a separate power supply, the jumpers across R-R1 and S-S1 must be removed. Otherwise 
the inverter may be damaged.
3. For a different power supply system, which takes the power of the control circuit from other than the 
primary side of the MC, the voltage should be equal to the main circuit voltage.
4. For the FR-V520-3.7K to 55K, FR-V540-3.7K to 55K, the power supply cables must not be connected 
to the lower terminals. If connected, the inverter may be damaged.
5. Supplying power to only the R1 and S1 terminals and entering the start signal will result in an error 
indication (E.OC1).
Terminal block for main circuit
1) Loosen the upper screws
2) Remove the lower screws.
3) Remove the jumpers.
R
S
T
R1
S1
4) Connect the separate power supply cables for control circuit to the 
    lower terminals (R1, S1). (Note 4)
MC
Power supply terminal 
block for control circuit
Main power supply
Power supply terminal
block for control circuit
R
S
T
R1 S1
1) Loosen the upper screws.
2) Remove the lower screws.
3) Pull out and remove the jumper.
4) Connect the separate power supply 
    cables for control circuit to the 
    upper terminals (R1, S1). (Note 4)