1.6.7
Harmonic suppression guidelines
Harmonic currents flow from the inverter to a power receiving point via a power transformer. The harmonic 
suppression guidelines were established to protect other consumers from these outgoing harmonic currents.
The three-phase 200V input specifications 3.7kW or less are previously covered by "Harmonic suppression 
guideline for household appliances and general-purpose products" and other models are covered by "Harmonic 
suppression guideline for consumers who receive high voltage or special high voltage". However, the general-
purpose inverter has been excluded from the target products covered by "Harmonic suppression guideline for 
household appliances and general-purpose products" in January 2004. Later, this guideline was repealed on 
September 6, 2004. All capacities of all models are now target products of "Harmonic suppression guideline for 
consumers who receive high voltage or special high voltage" (hereinafter referred to as "guideline for specific 
consumers").
"Guideline for specific consumers"
This guideline sets forth the maximum values of harmonic currents outgoing from a high-voltage or especially 
high-voltage consumer who will install, add or renew harmonic generating equipment. If any of the maximum 
values is exceeded, this guideline requires that consumer to take certain suppression measures.
(1) Application of the guideline for specific consumers
Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power
Received 
Power Voltage
5th
7th
11th
13th
17th
19th
23rd
Over 23rd
6.6kV
3.5
2.5
1.6
1.3
1.0
0.9
0.76
0.70
22kV
1.8
1.3
0.82
0.69
0.53
0.47
0.39
0.36
33kV
1.2
0.86
0.55
0.46
0.35
0.32
0.26
0.24
Table 2 Conversion Factors for FR-V500 Series
Class
Circuit Type
Conversion Factor Ki
3
Three-phase bridge
(Capacitor-smoothed)
Without reactor
K31 = 3.4
With reactor (AC side)
K32 = 1.8
With reactor (DC side)
K33 = 1.8
With reactors (AC, DC sides)
K34 = 1.4
5
Self-excitation three-phase 
bridge
When high power factor converter is used
K5 = 0
Table 3 Equivalent Capacity Limits
Received Power Voltage
Reference Capacity
6.6kV
50kVA
22/33kV
300kVA
66kV or more
2000kVA
Harmonic suppression 
technique is not required.
New installation/addition/
renewal of equipment
Calculation of equivalent 
capacity sum
Not more than 
reference capacity
         Sum of 
equivalent capacities
Over reference capacity
Calculation of outgoing 
harmonic current
            Is outgoing 
harmonic current equal to 
or lower than maximum 
               value?
Over maximum value
Harmonic suppression 
technique is not required.
Not more than 
maximum value