26
Input terminals
1.7 Input terminals
1.7.1
Run (start) and stop (STF, STR, STOP)
To start and stop the motor, first switch on the input power of the inverter (when there is a magnetic contactor on the 
input side, use the operation-ready switch to turn on the magnetic contactor), then start the motor with the forward 
or reverse rotation start signal.
(1)  Two-wire type (STF, STR)
A two-wire type connection is shown on the right.
1)
The forward/reverse rotation signal is used as both 
the start and stop signals. Turn on either of the 
forward and reverse rotation signals to start the 
motor in the corresponding direction. Turn on both or 
turn off the start signal during operation to decelerate 
the inverter to a stop.
2)
The speed setting signal may either be given by 
entering 0 to 10VDC across the speed setting input 
terminal 2-5 or by setting the required values in Pr. 4 
to Pr. 6 "three-speed setting" (high, middle, low 
speeds). (Refer to page 77 for three-speed 
operation.)
Two-Wire Type Connection Example
(2)  Three-wire type (STF, STR, STOP)
A three-wire type connection is shown on the right. Assign 
the start self-holding signal (STOP) to any of the input 
terminals.
1)
Short signals STOP-SD to enable the start self-holding 
function. In this case, the forward/reverse rotation 
signal functions only as a start signal.
2)
If the start signal terminals STF (STR)-SD are once 
shorted, then opened, the start signal is kept on and 
starts the inverter. To change the rotation direction, 
short the start signal STR (STF)-SD once, then open it.
3)
The inverter is decelerated to a stop by opening 
terminals STOP-SD once. The three-wire connection 
is shown on the right.
4)
When terminals JOG-SD are shorted, the STOP signal 
is invalid and jog signal has precedence.
5)
If the output stop terminals MRS-SD are shorted, the 
self-holding function is not deactivated.
Three-Wire Type Connection Example
Power 
supply
MCCB
Forward 
rotation start
Reverse 
rotation start
STF
STR (Pr.187 = "9999")
SD
Across STF-SD
(STR)
ON
Time
O
utp
ut sp
eed
Inverter
R, S, T
REMARKS
Assign the STOP signal to any of Pr. 180 to Pr. 183 and 
Pr. 187 (input terminal function selection).
MCCB
Time
Power
supply
Stop
Forward rotation 
start
Reverse rotation 
start
STF
STR (Pr.187 = "9999")
SD
STOP
Start
Stop
ON
ON
(Set "25" in any of 
Pr. 180 to Pr. 183)
Output speed
Inverter
R, S, T