38
Using the second motor
1.11 Using the second motor
1.11.1 Wiring diagram (second motor)
1.11.2  Second motor setting parameters
z Turn on/off the RT signal to switch between the first and second motors using contacts information of the 
magnetic contactor (MC).
(Use the RT signal after setting it to any of the DI1 to DI4 signals using Pr. 180 to Pr. 183, Pr. 187 (input terminal 
function selection).
z Select V/F control for the Pr. 451 setting. Vector control with encoder can not be selected.
z By setting values other than "9999" in Pr. 451 when Pr. 450 = "9999" (factory setting), the control system of the first 
motor can be changed by switching the RT terminal on and off. 
 
(In this case, turning the RT signal on makes the second function of Pr. 44, Pr. 45, Pr. 452, and Pr. 830 to Pr. 837 valid.)
Param
eter
Name
Factory 
Setting
Setting Range
0
Mitsubishi standard motor (SF-JR)
Inverter internal 
constant
10
Mitsubishi constant torque motor 
 
(SF-HRCA)
Inverter internal 
constant
Refer to
450
Second applied motor
9999
30
SF-V5RU dedicated motor 
 
(includes SF-VR type motor)
Inverter internal 
constant
9999
Function invalid
 
 Pr. 71 "applied motor" is made valid.
451
Second motor control 
method selection
9999
20
V/F control
Speed control
9999
Function invalid 
 
The setting is the same as that of control system of Pr. 800 "control 
system selection". (*)
452
Second electronic 
thermal O/L relay
9999
Set the rated motor current.
0 to 500A (Refer to page 80.)
9999
Function invalid
453
Second motor 
capacity
Inverter 
capacity
Set the motor capacity.
0.4 to 55kW
Setting can 
be made 
when 
 
Pr. 450
   
"9999"
454
Number of second 
motor poles
4
Set the number of motor poles.
2, 4, 6P
CAUTION
* Even when the first motor is under vector control, the second motor is V/F controlled while the RT 
signal is on independently of the Pr. 451 setting when Pr. 450   "9999".
CAUTION
1. Provide interlocks to prevent the MC1 and MC2 
from being turned on simultaneously.
2. For the second motor (motor without encoder), 
use Pr. 452 "second electronic thermal O/L relay" 
or provide an external thermal relay.
3. *: Give one external thermal relay signal to across 
 
OH-SD.
Related parameters
Second electronic thermal relay function setting 
⇒ (Pr. 452 "second 
electronic thermal O/L relay" (Refer to page 80.))
Inverter
Motor without encoder
(Second motor)
MC2
MC1
V
W
OH
SD
PA
PAR
PB
PBR
PZ
PZR
PG
SD
U
IM
*
U
V
W
E
IM
U
V
W
E
Encoder
Mitsubihi dedicated motor 
(SF-V5RU) (First motor)
Thermal
protector
G1
G2
A
B
C
D
G
S
R
F
N