66
Parameter list
3.1 Parameter list
The inverter is factory-set to display only the simple mode parameters.
Set Pr. 160 "extended function selection" as required.
Parameter
Name
Factory 
Setting
Setting 
Range
Remarks
160
Extended function 
selection
0
0
Accessible to only the simple mode parameters.
1
Accessible to all parameters.
CAUTION
• The blacked out parameters in the table below indicate simple mode parameters.
• The shaded parameters in the table allow its setting to be changed during operation even if "0" (factory 
setting) is set in Pr. 77 (parameter write disable selection).
• *: Accessible when Pr. 77 = 801.
Function
Parameter 
No.
Name
Setting Range
Minimum
Setting
Increments
Factory Setting
Refer 
To
Custo
mer 
Setting
Basic functions
0
Torque boost (manual) 
0 to 30%
0.1%
4%/3%/2%
(3.7K or less/
5.5K, 7.5K/
11K or more)
1
Maximum speed
0 to 3600r/min
1r/min
1500r/min
2
Minimum speed
0 to 3600r/min
1r/min
0r/min
3
Base frequency
10 to 200Hz
0.01Hz
60Hz
4
Multi-speed setting (high speed)
0 to 3600r/min
1r/min
1500r/min
5
Multi-speed setting (middle speed)
0 to 3600r/min
1r/min
750r/min
6
Multi-speed setting (low speed)
0 to 3600r/min
1r/min
150r/min
7
Acceleration time
0 to 3600s/0 to 
360s
0.1s/0.01s
5s/15s
(1.5K to 5.5K
/7.5K to 55K)
8
Deceleration time
0 to 3600s/0 to 
360s
0.1s/0.01s
5s/15s
(1.5K to 5.5K
/7.5K to 55K)
9
Electronic thermal O/L relay
0 to 500A
0.01A
0A
Standard 
operation 
functions
10
DC injection brake operation speed
0 to 1500r/min, 
9999
0.1r/min
15r/min
11
DC injection brake operation time
0 to 0.5s
0.1s
0.5s
12
DC injection brake voltage
0 to 30%
0.1%
4%/2%
(7.5K or less/
11K or more)
13
Starting speed
0 to 1500r/min
0.1r/min
15r/min
15
Jog speed setting
0 to 1500r/min
0.1r/min
150r/min
16
Jog acceleration/deceleration time
0 to 3600s/0 to 
360s
0.1s/0.01s
0.5s
Operation 
selection 
functions
17
MRS input selection
0, 2
1
0
19
Base frequency voltage
0 to 1000V, 8888, 
9999
0.1V
9999
20
Acceleration/deceleration reference 
speed
1 to 3600r/min
1r/min
1500r/min
21
Acceleration/deceleration time increments
0, 1
1
0
22
Torque limit level
0 to 400%
0.1%
150%
24
Multi-speed setting (speed 4)
0 to 3600r/min, 
9999
1r/min
9999
25
Multi-speed setting (speed 5)
0 to 3600r/min, 
9999
1r/min
9999
26
Multi-speed setting (speed 6)
0 to 3600r/min, 
9999
1r/min
9999
27
Multi-speed setting (speed 7)
0 to 3600r/min, 
9999
1r/min
9999
28
Multi-speed input compensation
0, 1
1
0
29
Acceleration/deceleration pattern
0, 1, 2, 3, 4
1
0
30
Regenerative function selection
0, 1, 2
1
0
31
Speed jump 1A
0 to 3600r/min, 
9999
1r/min
9999
32
Speed jump 1B
0 to 3600r/min, 
9999
1r/min
9999