Справочник Пользователя для Hitachi SJ700B
FUNCTION LIST
● MONITORING FUNCTIONS and MAIN PROFILE PARAMETERS
[⃝ = Allowed
×
= Not permitted]
Code
Function Name
Monitored data or setting
Default Setting
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
SJ700/SJ700D(CTmode)
SJ700B
-FE
-FU
-F
-F
-FU
Monitor Mode
d001
Output frequency monitor
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
-
-
-
-
-
⃝
-
d002
Output current monitor
0.0 to 999.9, 1000 to 9999 (A)
-
-
-
-
-
-
-
d003
Rotation direction minitoring
F (forward rotation), o (stopped), r (reverse rotation)
-
-
-
-
-
-
-
d004
Process variable (PV), PID feedback monitor
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999. 1000 to 9999 (10000 to 99990),
「100 to 「999 (10000 to 999000)
-
-
-
-
-
-
-
d005
Intelligent input terminal status
(Example) FW, 7, 2, 1 : ON
8, 6, 5, 4, 3 : OFF
8, 6, 5, 4, 3 : OFF
-
-
-
-
-
-
-
d006
Intelligent output terminal status
(Example) 12, 11 : ON
AL, 15, 14, 13 :OFF
AL, 15, 14, 13 :OFF
-
-
-
-
-
-
-
d007
Scaled output frequency monitoring
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)
-
-
-
-
-
⃝
-
d008
Actual-frequency monitoring (*3)
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
-
-
-
-
-
-
-
d009
Torque command monitoring (*3)
-200. to +200. (%)
-
-
-
-
-
-
-
d010
Torque bias monitoring (*3)
-200. to +200. (%)
-
-
-
-
-
-
-
d012
Torque monitoring
-200. to +200. (%)
-
-
-
-
-
-
-
d013
Output voltage monitoring
0.0 to 600.0 (V)
-
-
-
-
-
-
-
d014
Power monitoring
0.0 to 999.9 (kW)
-
-
-
-
-
-
-
d015
Cumulative power monitoring
0.0 to 999.9, 1000. to 9999.,1000 to 9999 (10000 to 99990), 「100 to 「999 (100000 to 999000)
-
-
-
-
-
-
-
d016
Cumulative operation RUN time monitoring
0. to 9999., 1000 to 9999 (10000 to 99990), 「100 to 「999 (10000 to 999000) (hr)
-
-
-
-
-
-
-
d017
Cumulative power-on time monitoring
0. to 9999., 1000 to 9999 (10000 to 99990), 「100 to 「999 (10000 to 999000) (hr)
-
-
-
-
-
-
-
d018
Heat sink temperature monitoring
-020. to 200.0 (℃)
-
-
-
-
-
-
-
d019
Motor temperature monitoring
-020. to 200.0 (℃)
-
-
-
-
-
-
-
d022
Life-check monitoring
1: Capacitor on main circuit board
2: Cooling-fan speed drop
2: Cooling-fan speed drop
-
-
-
-
-
-
-
d023
Program counter
0 to 1024
-
-
-
-
-
-
-
d024
Program number monitoring
0000 to 9999
-
-
-
-
-
-
-
d025
User monitor 0
-2147483647 to 2147483647 (upper 4 digits including “-“)
-
-
-
-
-
-
-
d026
User monitor 1
-2147483647 to 2147483647 (upper 4 digits including “-“)
-
-
-
-
-
-
-
d027
User monitor 2
-2147483647 to 2147483647 (upper 4 digits including “-“)
-
-
-
-
-
-
-
d028
Pulse counter
0 to 2147483647 (upper 4 digits)
-
-
-
-
-
-
-
d029
Position setting monitor (*3)
-1073741823 to 1073741823 (upper 4 digits including “-“)
-
-
-
-
-
-
-
d030
Position feedback monitor (*3)
-1073741823 to 1073741823 (upper 4 digits including “-“)
-
-
-
-
-
-
-
d031
Clock monitor (SJ700D only)
* In case you use WOP (option), this monitor is activated.
-
-
-
×
×
-
-
d060
Inverter mode monitor (SJ700D only)
I-C (CT) / I-v (VT)
-
-
-
×
×
-
-
d080
Trip Counter
0. to 9999., 1000 to 6553 (10000 to 65530) (times)
-
-
-
-
-
-
-
d081
-
d086
Trip monitoring 1-6
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
running time (hours), power-on time (hours)
-
-
-
-
-
-
-
d090
Programming error monitoring
Warning code
-
-
-
-
-
-
-
d102
DC voltage monitoring
0.0 to 999.9 (V)
-
-
-
-
-
-
-
d103
BRD load factor monitoring
0.0 to 100.0 (%)
-
-
-
-
-
-
-
d104
Electronic thermal overload monitoring
0.0 to 100.0 (%)
-
-
-
-
-
-
-
Setting Mode
F001
Output frequency setting
0.0, "start frequency" to "maximum frequency" (or maximum frequency,
2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
0.00
0.00
0.00
0.00
0.00
⃝
⃝
F002
Acceleration (1) time setting
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
30.00 30.00 30.00 30.00 30.00
⃝
⃝
F202
Acceleration (1) time setting, 2nd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
30.00 30.00 30.00 30.00 30.00
⃝
⃝
F302
Acceleration (1) time setting, 3rd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
30.00 30.00 30.00 30.00 30.00
⃝
⃝
F003
Deceleration (1) time setting
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
30.00 30.00 30.00 30.00 30.00
⃝
⃝
F203
Deceleration time setting, 2nd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
30.00 30.00 30.00 30.00 30.00
⃝
⃝
F303
Deceleration time setting, 3rd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
30.00 30.00 30.00 30.00 30.00
⃝
⃝
F004
Keypad Run key routing
00 (forward rotation), 01 (reverse rotation)
00
00
00
00
00
×
×
Expanded Function
A---
A Group: Standard functions
b---
b Group: Fine tuning functions
C---
C Group: Intelligent terminal functions
H---
H Group: Motor constants functions
P---
P Group: Expansion card functions
U---
U Group: User-selectable menu functions
(*1) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz) (*2) 4000HF: -120. to -100., -99.9 to 0.00 to 99.99,100.0 to 120.0 (Hz)
(*3) SJ700D (VT): Not available (no display)
(*3) SJ700D (VT): Not available (no display)
FW
5 4
8 7
2
3
6
1
ON
OFF
OFF
AL
12
13
11
15 14
ON
OFF
OFF
2 1
ON
OFF
OFF
14