Справочник Пользователя для Hitachi SJ700B
● H GROUP: MOTOR CONSTANTS FUNCTIONS
[⃝ = Allowed
×
= Not permitted]
Code
Function Name
Monitored data or setting
Default Setting
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
SJ700/SJ700D(CTmode)
SJ700B
-FE
-FU
-F
-F
-FU
Contr
ol constants
H001
Auto-tuning Setting
00 (disabling auto-tuning), 01 (auto-tuning without rotation),
02 (auto-tuning with rotation)
02 (auto-tuning with rotation)
00 00 00 00 00 ×
×
H002
Motor data selection, 1st motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
02 (auto-tuned data [with online auto-tuning function])
00 00 00 00 00 ×
×
H202
Motor data selection, 2nd motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
02 (auto-tuned data [with online auto-tuning function])
00 00 00 00 00 ×
×
H003
Motor capacity, 1st motor
SJ700/SJ700D:0.20 to 160 (kW), 185kW and over :11.0 to 400 (kW)
SJ700B:0.20 to 160(kW)
SJ700B:0.20 to 160(kW)
Factory set
×
×
H203
Motor capacity, 2nd motor
SJ700/SJ700D:0.20 to 160 (kW), 185kW and over :11.0 to 400 (kW)
SJ700B:0.20 to 160 (kW)
SJ700B:0.20 to 160 (kW)
×
×
H004
Motor poles setting, 1st motor
2, 4, 6, 8, 10 (poles)
4
4
4
4
4
×
×
H204
Motor poles setting, 2nd motor
2, 4, 6, 8, 10 (poles)
4
4
4
4
4
×
×
H005
Motor speed constant, 1st motor
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
1.590 1.590 1.590 1.590 1.590
⃝
⃝
H205
Motor speed constant, 2nd motor
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
1.590 1.590 1.590 1.590 1.590
⃝
⃝
H006
Motor stabilization constant, 1st motor
0. to 255.
100.
100.
100.
100.
100.
⃝
⃝
H206
Motor stabilization constant, 2nd motor
0. to 255.
100.
100.
100.
100.
100.
⃝
⃝
H306
Motor stabilization constant, 3rd motor
0. to 255.
100.
100.
100.
100.
100.
⃝
⃝
H020
Motor constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
Depending on
motor capacity/poles
×
×
H220
Motor constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
×
×
H021
Motor constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
×
×
H221
Motor constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
×
×
H022
Motor constant L, 1st motor
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
×
×
H222
Motor constant L, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
×
×
H023
Motor constant Io
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
×
×
H223
Motor constant Io, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
×
×
H024
Motor constant J
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
×
×
H224
Motor constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
×
×
H030
Auto constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
×
×
H230
Auto constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
×
×
H031
Auto constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
×
×
H231
Auto constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
×
×
H032
Auto constant L, 1st motor
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
×
×
H232
Auto constant L, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
×
×
H033
Auto constant Io, 1st motor
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
×
×
H233
Auto constant Io, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
×
×
H034
Auto constant J, 1st motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
×
×
H234
Auto constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
×
×
Contr
ol constants
H050
PI proportional gain for 1st motor
0.0 to 999.9, 1000.
100.0 100.0 100.0 100.0 100.0
⃝
⃝
H250
PI proportional gain for 2nd motor
0.0 to 999.9, 1000.
100.0 100.0 100.0 100.0 100.0
⃝
⃝
H051
PI integral gain for 1st motor
0.0 to 999.9, 1000.
100.0 100.0 100.0 100.0 100.0
⃝
⃝
H251
PI integral gain for 2nd motor
0.0 to 999.9, 1000.
100.0 100.0 100.0 100.0 100.0
⃝
⃝
H052
P proportional gain setting for 1st motor
0.01 to 10.00
1.00
1.00
1.00
1.00
1.00
⃝
⃝
H252
P proportional gain setting for 2nd motor
0.01 to 10.00
1.00
1.00
1.00
1.00
1.00
⃝
⃝
H060
Zero LV lmit for 1st motor (*4)
0.0 to 100.0
100.
100.
100.
70.
70.
⃝
⃝
H260
Zero LV lmit for 2nd motor (*4)
0.0 to 100.0
100.
100.
100.
70.
70.
⃝
⃝
H061
Zero LV starting boost current for 1st motor (*4) 0. to 50. (%)
50.
50.
50.
50.
50.
⃝
⃝
H261
Zero LV starting boozst current for 2nd motor (*4) 0. to 50. (%)
50.
50.
50.
50.
50.
⃝
⃝
H070
Terminal selection PI proportional gain setting 0.0 to 999.9, 1000.
100.0 100.0 100.0 100.0 100.0
⃝
⃝
H071
Terminal selection PI integral gain setting
0.0 to 999.9, 1000.
100.0 100.0 100.0 100.0 100.0
⃝
⃝
H072
Terminal selection P proportional gain setting 0.00 to 10.00
1.00
1.00
1.00
1.00
1.00
⃝
⃝
H073
Gain switching time
0. to 9999. (ms)
100.
100.
100.
100.
100.
⃝
⃝
(*1) 1850HF,2200HF,3150HF and 4000HF:0.1 to 999.9,1000. to 6553. (mΩ).
(*2) 1850HF,2200HF,3150HF and 4000HF:0.001 to 9.999,10.00. to 65.53 (mH).
(*3) 1850HF,2200HF,3150HF and 4000HF:0.01 to 0.35 “ rated current ” (A).
(*4) SJ700D (VT): Not available (no display)
(*2) 1850HF,2200HF,3150HF and 4000HF:0.001 to 9.999,10.00. to 65.53 (mH).
(*3) 1850HF,2200HF,3150HF and 4000HF:0.01 to 0.35 “ rated current ” (A).
(*4) SJ700D (VT): Not available (no display)
22