PROTECTIVE FUNCTIONS
37
z
z
z
z
Checking the inverter and converter modules
<Preparation>
(1) Disconnect the external power supply cables (R, S, T) <L
1
, L
2
, L
3
> and motor cables (U, V, W).
(2) Prepare a tester. (Use 100
Ω
 range.)
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R, S, T, U, V, W, P and N <L
1
, L
2
, L
3, 
U, V,
W, + and ->, and check for continuity.
Note: 1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of continuity, the measured value is several to several ten’s-of ohms depending on the
module type, circuit tester type, etc. If all measured values are almost the same, the modules are
without fault.
<Module device numbers and terminals to be checked>
Tester Polarity
Tester Polarity
Measured
Value
Measured
Value
R<L
1
>
P<+>
Discontinuity
R<L
1
>
N<->
Continuity
D1
P<+>
R<L
1
>
Continuity
D4
N<->
R<L
1
>
Discontinuity
S<L
2
>
P<+>
Discontinuity
S<L
2
>
N<->
Continuity
D2
P<+>
S<L
2
>
Continuity
D5
N<->
S<L
2
>
Discontinuity
T<L
3
>
P<+>
Discontinuity
T<L
3
>
N<->
Continuity
C
onverter m
odul
e
D3
P<+>
T<L
3
>
Continuity
D6
N<->
T<L
3
>
Discontinuity
U
P<+>
Discontinuity
U
N<->
Continuity
TR1
P<+>
U
Continuity
TR4
N<->
U
Discontinuity
V
P<+>
Discontinuity
V
N<->
Continuity
TR2
P<+>
V
Continuity
TR6
N<->
V
Discontinuity
W
P<+>
Discontinuity
W
N<->
Continuity
In
verter m
odul
e
TR5
P<+>
W
Continuity
TR2
N<->
W
Discontinuity
D1
D2
D3
D4
D5
D6
TR1
TR3
TR5
TR4
TR6
TR2
U
V
W
R
<L
1
>
S
<L
2
>
T
<L
3
>
C
P<+>
N
<->
Inverter module
Converter module