4.4.2
Simple magnetic flux vector control (Pr.80, Pr.90) 
<S MFVC>
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
(1) Automatically control optimum torque (Pr.80)
⋅ When Simple magnetic flux vector control is not used, set "9999" (initial value) in Pr.80.
⋅ Set the used motor capacity (equal to or one rank higher than the inverter capacity).
(2) Set the motor constant (Pr.90)
⋅ Normally setting is not necessary. When you need more torque under Simple magnetic flux vector control for other
manufacturer’s motor, set the motor primary resistance value (R1) for  connection. When the setting value is
"
9999" (initial value), the motor constant is based on the Mitsubishi motor constant (SF-JR, SF-HRCA).
Providing optimum excitation to the motor can also produce high torque in a low-speed range. 
(Simple magnetic flux vector control)
Parameter 
Number
Name
Initial
Value
Setting Range
Description
80
Motor capacity
9999
55K or lower
0.4 to 
55kW
Set the capacity of the motor used to 
select Simple magnetic flux vector 
control.
75K or higher
0 to 
3600kW
9999
V/F control is performed
90
Motor constant (R1)
9999
55K or lower
0 to 50
Ω Used to set the motor primary 
resistance value.
(Normally setting is not necessary.)
75K or higher
0 to 
400m
Ω
9999
Use the Mitsubishi motor (SF-JR, SF-
HRCA) constants
POINT
⋅ The number of motor poles should be any of 2, 4 and 6 poles.
⋅ Single-motor operation (One motor for one inverter)
⋅ The wiring length from inverter to motor should be within 30m
REMARKS
When using a constant-torque motor, set Pr. 71 Applied motor to "1" (constant-torque motor).
CAUTION
⋅ When Simple magnetic flux vector control is selected, the rated motor frequency is set in Pr. 3 and the rated motor voltage is set in
Pr. 19. The base frequency voltage is handled as 200V class : 200V, 400V class : 400V when "9999" or "8888" is set in Pr. 19 .
⋅ Adjustable 5 points V/F, energy saving operation mode, Optimum excitation control function only under V/F control. They do not
function for Simple magnetic flux vector control.
♦ Parameters referred to 
Pr. 3 Base frequency, Pr. 19 Base frequency voltage  
 Refer to page 98
Pr. 60 Energy saving control selection  
 Refer to page 176
Pr. 71 Applied motor  
 Refer to page 122
Pr. 77 Parameter write selection  
 Refer to page 200
S
 MFVC
S
 MFVC
S