106
Frequency setting by external terminals
4.7.3
Input compensation of multi-speed and remote setting (Pr. 28)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
4.7.4
Remote setting function (Pr. 59)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
* External operation frequency (other than multi-speed) or PU running frequency 
By inputting the frequency setting compensation signal (terminal 1, 2), the speed (frequency) can be compensated
for relative to the multi-speed setting or the speed setting by remote setting function.
Parameter 
Number
Name
Initial Value
Setting Range
Description
28
Multi-speed input 
compensation selection
0
0
Without compensation
1
With compensation
REMARKS
⋅ Select the compensation input voltage (0 to ±5V, 0 to ±10V) and used terminal (terminal 1, 2) using Pr. 73 Analog input selection.
♦ Parameters referred to 
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239 (multi-speed operation)  
 Refer to page 102
Pr. 73 Analog input selection  
 Refer to page 185
Pr. 59 Remote function selection  
 Refer to page 106
Even if the operation panel is located away from the enclosure, you can use contact signals to perform
continuous variable-speed operation, without using analog signals.
By simply setting this parameter, you can use the acceleration, deceleration and setting clear functions of
the motorized speed setter (FR-FK).
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
RH, RM, RL 
Signal Function
Frequency Setting 
Storage Function
Deceleration to the 
Frequency Lower 
Than the Set 
Frequency
59
Remote function 
selection
0
0
Multi-speed setting
1
Remote setting
Used
Disabled
2
Remote setting
Not used
Disabled
3
Remote setting
Not used
(Turning STF/STR 
OFF clears remotely- 
set frequency.)
Disabled
11
Remote setting
Used
Enabled
12
Remote setting
Not used
Enabled
13
Remote setting
Not used
(Turning STF/STR 
OFF clears remotely-
set frequency.)
Enabled
Acceleration
Deceleration
Clear
Inverter
STF
RH
RM
10
2
5
RL
Connection 
diagram for remote setting
Forward 
rotation
SD
Deceleration 
(RM)
Clear (RL)
Acceleration 
(RH)
Forward 
rotation (STF)
ON
ON
Power supply
ON
0Hz
*
ON
ON
ON
ON
ON
ON
When 
Pr. 59 = 1, 11
When 
Pr. 59 = 2, 3, 12, 13
ON
ON
Output frequency 
(Hz)
When 
Pr. 59 = 1, 2, 11, 12
When 
Pr. 59 = 3, 13
Time