Function assignment of external 
4.11.7 Output current detection function 
(Y12 signal, Y13 signal, Pr. 150 to Pr. 153, Pr. 166, Pr. 167)
The output current during inverter running can be detected and output to the output terminal.
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
150
Output current detection 
level
120%
0 to 150%
Set the output current detection level. 100% is the 
rated inverter current.
151
Output current detection 
signal delay time
0s
 0 to 10s
Set the output current detection period. Set the 
time from when the output current has risen above 
the setting until the output current detection signal 
(Y12) is output.
152
Zero current detection level
5%
0 to 150%
Set the zero current detection level. The rated 
inverter current is assumed to be 100%.
153
Zero current detection time
0.5s
 0 to 10s
Set the time period from when the output current 
drops below the Pr. 152 value until when the zero 
current detection signal (Y13) is output.
166
Output current detection 
signal retention time
0.1s
 0 to 10s
Set the retention time when the Y12 signal is ON.
9999
The Y12 signal ON status is retained. The signal is 
turned OFF at the next start.
167
Output current detection 
operation selection
0
0
Y12 Signal - ON
Y13 Signal - ON
Operation continued
Operation continued
1
Fault stop (E.CDO)
Operation continued
10
Operation continued
Fault stop (E.CDO)
11
Fault stop (E.CDO)
Fault stop (E.CDO)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
(1) Output current detection (Y12 signal, Pr. 150, Pr.
151, Pr. 166, Pr. 167)
⋅ The output power detection function can be used for excessive
torque detection, etc.
⋅ If the output current remains higher than the Pr. 150 setting during
inverter operation for longer than the time set in Pr. 151, the
output current detection signal (Y12) is output from the inverter's
open collector or relay output terminal. 
⋅ When the Y12 signal turns ON, the ON state is held for the time
set in Pr. 166 .
⋅ When Pr. 166  = "9999", the ON state is held until a next start.
⋅ At the Pr. 167 setting of "1" or "11", the inverter output is stopped
and the output current detection fault (E.CDO) is displayed when
the Y12 signal turns ON. When a fault stop occurs, the Y12
signal is ON for the time set in Pr. 166 at the Pr. 166 setting of
other than "9999", and remains ON until a reset is made at the Pr.
166
 setting of "9999". Setting Pr. 167 = "1" or "11" at Y12 signal
ON does not cause E.CDO. Setting to Pr. 167 becomes effective
after Y12 is turned OFF.
⋅ For the X12 signal, set "12 (positive logic)" or "112 (negative
logic)" in any of Pr. 190 to Pr. 196 (output terminal function selection)
and assign the function to the output terminal.
Time
Pr. 150
OFF
ON
OFF
Output current 
detection signal
(Y12)
Pr. 166
Minimum 0.1s 
(initial value)
Output current
Pr. 166     9999, Pr. 167 = 0
Pr. 151