64
Parameter list
4.2 Parameter list
4.2.1
Parameter list
In the initial setting, only the simple mode parameters are displayed.
Set Pr. 160 User group read selection as required.
To use the inverter under IPM motor control, refer to page 77.
Parameter
Name
Initial 
Value
Setting 
Range
Remarks
160
User group read 
selection
9999
9999
Only the simple mode parameters can be displayed.
0
Simple mode and extended mode parameters can be 
displayed.
1
Only the parameters registered in the user group can be 
displayed.
REMARKS
⋅ The parameters marked   are the simple mode parameters.
⋅ The parameters marked with 
 in the table allow their settings to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection.
⋅ Refer to the appendix 2 (page 368) for instruction codes for communication and availability of parameter clear, all clear, and
parameter copy of each parameter.
......... Specifications differ according to the date assembled. Refer to page 378 to check the SERIAL number.
Function Parameters
Name
Setting Range
Minimum 
Setting 
Increments
Initial 
Value
Refer 
to 
Page
Customer 
Setting
Ba
si
c f
u
nc
tion
s
 0
Torque boost
0 to 30%
0.1%
6/4/3/2/
1.5/1%
 1
Maximum frequency
0 to 120Hz
0.01Hz
120/60Hz
 
 2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
 3
Base frequency
0 to 400Hz
0.01Hz
60Hz
 4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
 5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
 6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
 7
Acceleration time
0 to 3600/ 360s
0.1/0.01s
5s/15s
 8
Deceleration time
0 to 3600/ 360s
0.1/0.01s
10s/30s
 9
Electronic thermal O/L relay
0 to 500/0 to 3600A
0.01/0.1A
Rated 
inverter 
current
DC in
je
ct
io
n
 
br
a
ke
10
DC injection brake operation 
frequency
0 to 120Hz, 9999
0.01Hz
3Hz
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
12
DC injection brake operation voltage
0 to 30%
0.1%
4/2/1%
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
14
Load pattern selection
0, 1
1
1
Jog
 
op
er
at
ion
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
17
MRS input selection
0, 2, 4
1
0
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120/60Hz
 
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999