2. EXPLANATION OF MODULE FUNCTIONS
2.7 HR877/879 Card
II - 12
[Connector layout diagram]
OUT
IN
T
R
T
R
NETWORK
x 100 x 10
x 10
x 1
x 1
GROUP STATION
DIPSW
MODE
ISP
[Explanation of settings]
NETWORK : Network No. setting switch
Set the network number between 1 and 239 with the three rotary switches. The I/F board group No. is the
number used when setting the local station network number if connecting to MELSECNET/10.
number used when setting the local station network number if connecting to MELSECNET/10.
×100 switch
: Set the 100th place of the network number.
×10 switch
: Set the 10th place of the network number.
×1 switch
: Set the 1st place of the network number.
Set within the range of 1 to 239. (Default setting ×100: 0 ×10: 0 ×1: 1)
GROUP
: Group No. setting switch
Set the group number with the rotary switch. The I/F board group No. is the number used when setting the
local stations' group No. if connecting to MELSECNET/10.
Set within the range of 1 to 9. 0 means that no group is designated. (Default setting: 0)
local stations' group No. if connecting to MELSECNET/10.
Set within the range of 1 to 9. 0 means that no group is designated. (Default setting: 0)
STATION
: Station number setting switch
Set the station numbers between 01 and 64 with the two rotary switches. The I/F board group No. is the
number used when setting the local station number (normal station) if connecting to MELSECNET/10.
number used when setting the local station number (normal station) if connecting to MELSECNET/10.
×10 switch
: Set the 10th place of the station number.
×1 switch
: Set the 1st place of the station number.
Set within the range of 1 to 64. (Default setting ×10: 0 ×1: 1)
MODE
: Mode setting switch
0: Online (automatic parallel-off valid)
1: Online (automatic parallel-off invalid)
1: Online (automatic parallel-off invalid)
OFF
ON
2: Offline
SW1
: PC-PC network
Remote I/O network
3 to 9: Test mode
SW2
: Normal station
Control station
D: Network No. confirmation SW3
: Common parameter
Default parameter
E: Group No. confirmation
SW4, 5
: Number of stations
F: Station No. confirmation
off, off on, off off, on on, on
8 stations 16 stations 32 stations 64 stations
SW6, 7
: Size
off, off on, off off, on on, on
2K point 4K point 6K point 8K point
(Default
setting:
0)
DIPSW
: Network condition setting
This switch is used to set the MELSECNET/10 operation conditions.
This switch is not used currently. (Always OFF) (Default setting: All OFF)
This switch is not used currently. (Always OFF) (Default setting: All OFF)
[Explanation of LEDs]
RUN
: (Green) ON when normal
F.ERR : (Red) ON when main (forward) loop hardware error occurs
R.ERR : (Red) ON when sub (reverse) loop hardware error occurs
F.SD
R.ERR : (Red) ON when sub (reverse) loop hardware error occurs
F.SD
: (Green) ON during main (forward) loop transmission
F.RD
: (Green) ON during main (forward) loop reception
R.SD
: (Green) ON during sub (reverse) loop transmission
R.RD
: (Green) ON during sub (reveres) loop reception