3. INSTALLATION 
3.4  Noise Countermeasures 
 
 
I - 14 
The cables connected to the control unit for which the shield must be connected to the ground are shown 
below. 
 
Unit name 
Connector name 
Application/function 
Cable shield treatment
SERVO1 
Servo drive unit/spindle drive unit 
Required 
SERVO2 
Auxiliary axis 
Required 
HANDLE 
Manual pulse generator 
Required 
ENC 
Synchronous feed encoder 
Required 
SIO 
RS-232C 
Required 
TERMINAL 
Communication terminal 
Required 
SKIP 
Sensor signal 
Required 
DIO 
Machine input/output signal 
Not required 
RIO-M 
Remote I/O unit 
Required 
Control unit 
(FCU6-MU043) 
(FCU6-MU042) 
(FCU6-MU041) 
RIO-M/S 
Remote I/O unit 
Required 
 
 
 
3.4.3  Connection of Spark Killer 
 
The noise generated when the coil/contact operates must be removed. 
As a countermeasure, connect a spark killer in parallel with the coil/contact. 
 
 
Coil
 
Contact
E
 
SK
SK
 
 
 
 
The CR compound element is effective in removing the noise generated due to magnetic induction. 
Spark killer 
C:  0.033 to 0.1
µF
 
R:  10 to 120
Ω