4. CONTROL UNIT CONNECTIONS 
4.10    Connecting the RS-232C Device 
 
 
I - 34 
4.10    Connecting the RS-232C Device 
The SIO connector is used to connect the RS-232C device (serial I/O). 
The F310 and F311 relay cables are required to connect the RS-232C cable. (Refer to the CABLE 
MANUFACTURING DRAWINGS for details.) 
 
SIO 
LED1 
Control unit 
1
 
10
 
11
 
20
 
SIO 
connector 
pin No.
 
F311 cable
F310 cable
RS-232C relay
or
RS-232C/RS-422
(For GPP)relay 
RS-232C device
MELSEC perfipheral device connection connector
(Note) When connecting GPP with RS-232C, use 
a conversion cable, and connect to the 
TERMINAL connector.
 
Cabinet side wall
The specifications of the cross cable are shown below. 
Cross cable connection
For DC code control
Panel relay 
connector side
RS-232C  
device side 
1  GND
2  TXD
3  RXD
1  GND 
2  TXD 
3  RXD 
4  RTS 
5  CTS 
6  DSR 
20  DTR 
7  GND 
1  GND 
2  TXD 
3  RXD 
4  RTS 
5  CTS 
6  DSR 
20  DTR 
7  GND 
1  GND
2  TXD
3  RXD
4  RTS
5  CTS
6  DSR
20  DTR
7  GND
6  DSR
20  DTR
7  GND
For RS/CS code control
RS-232C 
device side 
Recommended adaptive connector 
Connector  : HDBB-25PF(05)(Hirose Electric) 
Case 
: HDB-CTF(Hirose Electric) 
<Caution>  
• Do not connect anything to the open pins.   
• Keep the total cable length at 15m or less. 
Cross cable
Cross cable
Maximum cable length:15m
RS
232C
RS
422
Panel relay 
connector side
 
 CAUTION 
 
  Incorrect connections could cause device damage, so always connect the cables to the 
designated connectors. 
 
  Do not connect or disconnect the connection cable between each unit while the power 
is ON. 
 
  Separate the signal wire from the drive line/power line when wiring.