Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-12
Command Module and Drive Module Site Preparation Guide
Site Wiring
The drive modules use wide-ranging, redundant power supplies that automatically 
accommodate voltages to the AC power source. The power supplies operate at a range 
between 90 VAC and 264 VAC, and at a minimum frequency of 50 Hz and a maximum 
frequency of 60 Hz. The power supplies meet standard voltage requirements for both 
domestic (inside USA) and international (outside USA) operation. They use standard 
industrial wiring with line-to-neutral or line-to-line power connections.
Consider the following information when preparing the drive module installation site:
Earth ground – The unit must be properly grounded, including an earth ground 
conductor on the AC power source.
Circuit overloading – Ensure the power circuits and associated circuit breakers in the 
cabinet and building provide sufficient power and overload protection. To prevent 
possible damage to the unit, isolate its power source from large switching loads (such as 
air conditioning motors, elevator motors, and factory loads).
Power interruptions – The drive modules will withstand the following applied voltage 
interruptions (with or without an integrated UPS): 
Input transient – 50% of nominal voltage
Duration – one half cycle 
Frequency – once every 10 seconds
Power failures – After a total power failure, the unit will automatically perform a 
power-up recovery sequence without operator intervention after power is restored.