Справочник Пользователя для Mitsubishi Electronics QD75P4

Скачать
Страница из 860
 
 
 
10 - 8 
MELSEC-Q
10   HIGH-LEVEL POSITIONING CONTROL 
 
10.3.2 Block start (normal start) 
In a "block start (normal start)", the positioning data groups of a block are continuously 
executed in a set sequence starting from the positioning data set in "   Da.12   Start 
data No." by one start. 
 
Section [2] shows a control example where the " block start data" and "positioning 
data" are set as shown in section [1].   
 
[1]   Setting examples 
 
(1) Block start data setting example 
 
Axis 1 block 
start data 
 Da.11 
 
Shape 
 Da.12 
 
Start data No.
 Da.13 
 
Special start 
instruction 
 Da.14 
 
Parameter 
1st point 
1: Continue 
0: Block start 
– 
2nd point 
1: Continue 
0: Block start 
– 
3rd point 
1: Continue 
0: Block start 
– 
4th point 
1: Continue 
10 
0: Block start 
– 
5th point 
0: End 
15 
0: Block start 
– 
 
 
 
 
 
 
 
 
 
 
 
(2)      Positioning data setting example 
 
Axis 1 position-
ing data No. 
 Da.1 
 
Operation pattern 
 
1 00: 
Positioning 
complete 
 
 
11: Continuous path control 
1 block
1 block
 
01: Continuous positioning control
4 00: 
Positioning 
complete 
11: Continuous path control 
6 00: 
Positioning 
complete 
 
 
 
 
10 00: 
Positioning 
complete 
 
 
 
 
 
 
15 00: 
Positioning 
complete 
 
 
 
 
 
 
 
REMARK 
Block   : 
"1 block" is defined as all the data continuing from the positioning data in which 
"continuous positioning control" or "continuous path control" is set in the operation 
pattern ( Da.1 ) to the positioning data in which "independent positioning control 
(Positioning complete)" is set.