11 - 21 
MELSEC-Q
11   MANUAL CONTROL 
 
11.3.4 Creating a program to enable/disable the inching operation 
A sequence program must be created to execute an inching operation.    Consider the 
"required control data setting", "start conditions", and "start time chart" when creating 
the program. 
The following shows an example when an inching operation is started for axis 1. (The 
example shows the inching operation when a "10.0 µm" is set in "   Cd.16   Inching 
movement amount".) 
 
  Required control data setting 
 
The control data shown below must be set to execute an inching operation.    The 
setting is carried out with the sequence program. 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address
Axis 
Axis 
Axis 
Axis 
 Cd.16  
Inching movement 
amount 
100 
Set the setting value so that the command 
pulse is not increased larger than the maximum 
output pulse. 
(The max. output pulse 
QD75D N: 4Mpps 
QD75D : 1Mpps 
QD75P N/QD75P : 200kpps) 
1517 1617 1717 1817
 
  Refer to Section 5.7 "List of control data" for information on setting details. 
 
 Start conditions 
 
The following conditions must be fulfilled when starting.    The required conditions 
must also be assembled in the sequence program, and the sequence program 
must be configured so the operation will not start if the conditions are not fulfilled. 
 
Signal name 
Signal state 
Device 
Axis 
Axis 
Axis 
3
Axis 
4
Interface 
signal 
PLC READY signal 
ON
CPU module preparation 
completed 
Y0 
QD75 READY signal 
ON QD75 preparation completed 
X0 
Synchronization flag 
ON
Accessible to QD75 buffer 
memory 
X1 
Axis stop signal 
OFF Axis stop signal is OFF 
Y4  Y5  Y6
Y7
Start complete signal 
OFF Start complete signal is OFF 
X10  X11  X12 X13
BUSY signal 
OFF QD75 is not operating 
XC  XD  XE
XF
Positioning complete 
signal 
OFF
Positioning complete signal is 
OFF 
X14 X15 X16 X17
Error detection signal 
OFF There is no error 
X8  X9  XA
XB
M code ON signal 
OFF M code ON signal is OFF 
X4  X5  X6
X7
External 
signal 
Drive unit READY signal ON Drive unit preparation completed 
– 
Stop signal 
OFF Stop signal is OFF 
– 
Upper limit (FLS)   
ON Within limit range 
– 
Lower limit (RLS)   
ON Within limit range 
– 
 
  If the CPU module is set to the asynchronous mode in the synchronization setting, this must be 
inserted in the program for interlocking.    If it is set to the synchronous mode, it must not be 
inserted in the program for interlocking because it is turned ON when the CPU module executes 
calculation.