11 - 32 
MELSEC-Q
11   MANUAL CONTROL 
 
11.4.4 Creating a program to enable/disable the manual pulse generator operation   
A sequence program must be created to execute a manual pulse generator operation. 
Consider the "required control data setting", "start conditions" and "start time chart" 
when creating the program.   
The following shows an example when a manual pulse generator operation is started 
for axis 1. 
 
  Required control data setting 
 
The control data shown below must be set to execute a manual pulse generator 
operation. The setting is carried out with the sequence program.   
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address
Axis 
Axis 
Axis 
Axis 
 Cd.20  
Manual pulse 
generator 1 pulse 
input magnification 
Set the manual pulse generator 1 pulse input 
magnification. 
(QD75P N/QD75D N: 1 to 1000 times 
 QD75P /QD75D : 1 to 100 times) 
1522 
1523 
1622 
1623 
1722
1723
1822
1823
 Cd.21  
Manual pulse 
generator enable 
flag 
1 (0) 
Set "1: Enable manual pulse generator 
operation". (Set "0: Disable manual pulse 
generator operation" when finished with the 
manual pulse generator operation.) 
1524 1624 1724 1824
 
                                    Refer to Section 5.7 "List of control data" for details on the setting details. 
 
 Start conditions  
 
The following conditions must be fulfilled when starting. The required conditions 
must also be assembled in the sequence program, and the sequence program 
must be configured so the operation will not start if the conditions are not fulfilled.   
 
Signal name 
Signal state 
Device 
Axis 
Axis 
Axis 
3
Axis 
4
Interface 
signal 
PLC READY signal 
ON
CPU module preparation 
completed 
Y0 
QD75 READY signal 
ON QD75 preparation completed 
X0 
Synchronization flag 
ON
QD75 buffer memory 
The access is possible. 
X1 
Axis stop signal 
OFF Axis stop signal is OFF 
Y4  Y5  Y6
Y7
Start complete signal 
OFF Start complete signal is OFF 
X10  X11  X12 X13
BUSY signal 
OFF QD75 is not operating 
XC  XD  XE
XF
Error detection signal 
OFF There is no error 
X8  X9  XA
XB
M code ON signal 
OFF M code ON signal is OFF 
X4  X5  X6
X7
External 
signal 
Drive unit READY signal ON Drive unit preparation completed 
– 
Stop signal 
OFF Stop signal is OFF 
– 
Upper limit (FLS)   
ON Within limit range 
– 
Lower limit (RLS)   
ON Within limit range 
– 
 
 If the CPU module is set to the asynchronous mode in the synchronization setting, this must be 
inserted in the program for interlocking.    If it is set to the synchronous mode, it must not be 
inserted in the program for interlocking because it is turned ON when the CPU module executes 
calculation.