12 - 23 
MELSEC-Q
12   CONTROL SUB FUNCTIONS 
 
12.3.4 Output timing selection of near pass control 
The function "output timing selection of near pass control" allows the user to select the 
timing to output the difference (
) between the actual and the set positioning end 
addresses in continuous path control, in which the difference (
) is output during the 
execution of the next positioning data. 
 
The details shown below explain about the function "output timing selection of near 
pass control". 
  [1] Control details 
  [2] Control precautions 
  [3] Setting method 
 
[1]   Control details 
There are two options for an output timing of near pass control: "At constant 
speed" and "At deceleration". 
 
• At constant speed: The distance 
  is output when the next positioning data 
is executed in constant speed. 
• At deceleration: The distance 
  is output when the next positioning speed 
decelerates from V1 to V2. 
 
When "At constant speed" is selected in a condition where the specified speed of 
positioning data No.1 and No.2 in the figure 12.14 are "V1 > V2", the distance 
  is output when the next positioning data is executed in constant speed; 
therefore, the positioning execution time is extended. 
When "At deceleration" is selected, the positioning execution time is not 
extended and remains the same as it was set. 
 
The following drawing shows the operation of the function "output timing 
selection of near pass control".