6      SEQUENCE PROGRAM USED FOR POSITIONING CONTROL 
 
6.5.6 Stop program 
The axis stop signal [Y4, Y5, Y6, Y7] or a stop signal from an external source is used 
to stop the control. 
Create a program to turn ON the axis stop signal [Y4, Y5, Y6, Y7] as the stop program. 
 
The process for stopping control is explained below. 
Each control is stopped in the following cases. 
 
(1)    When each control is completed normally. 
(2)    When the drive unit READY signal is turned OFF. 
(3)    When a CPU module error occurs 
(4)    When the PLC READY signal is turned OFF. 
(5)    When an error occurs in QD75. 
(6)    When control is intentionally stopped   
(Stop signal from CPU module turned ON, stop signal from peripheral devices) 
 
The stop process for the above cases is shown below. 
(Excluding item (1) above "When each control is completed normally".) 
 
[1] Stop 
process 
 
Stop cause 
Stop 
axis 
M code 
ON 
signal 
after stop
Axis 
operation 
status 
( Md.26 ) 
after 
stopping
Stop process 
OPR control 
Major 
positioning 
control 
High-level 
positioning 
control 
Manual control 
Machine 
OPR 
control
Fast OPR 
control
JOG/ 
Inching 
operation 
Manual 
pulse 
generator 
operation
Forced stop 
Drive unit 
READY signal 
OFF 
Each 
axis 
No 
change 
Error Immediate 
stop 
Deceleration 
stop 
Fatal stop   
(Stop group 1) 
Hardware stroke 
limit upper/lower 
limit error 
occurrence 
Each 
axis 
No 
change 
Error 
Deceleration stop/sudden stop   
(Select with "   Pr.37   Stop group 1 sudden stop 
selection". 
Deceleration 
stop 
Emergency stop   
(Stop group 2) 
CPU module 
error occurrence
All axes 
No 
change 
Error 
Delegation stop/sudden stop   
(Select with "   Pr.38   Stop group 2 sudden stop 
selection". 
Deceleration 
stop 
PLC READY 
signal OFF 
Turns 
OFF 
Error in test 
mode 
No 
change 
Relatively safe 
stop  
(Stop group 3) 
Axis error 
detection (Error 
other than stop 
group 1 or 2) 
Each 
axis 
No 
change 
Error 
Deceleration stop/sudden stop   
(Select with "   Pr.39   Stop group 3 sudden stop 
selection". 
Deceleration 
stop 
"Stop" input from 
peripheral device
Intentional stop 
(Stop group 3) 
"Stop signal" ON 
from external 
source 
Each 
axis 
No 
change 
Stopped 
(Standby)
"Axis stop signal" 
ON from CPU 
module