11   MANUAL CONTROL 
 
11.2.5 JOG operation example 
  When the "stop signal" is turned ON during JOG operation 
 
When the "stop signal" is turned ON during JOG operation, the JOG operation will 
stop by the "deceleration stop" method.   
An error "Stop signal ON at start" (error code 106) will occur if JOG start signal is 
turned ON while the stop signal is ON. 
The operation can be started by turning the stop signal OFF, and turning the JOG 
start signal from OFF to ON again.   
 
OFF
ON
BUSY signal[XC, XD, XE, XF] OFF
ON
A JOG start signal OFF      ON 
while the stop signal is ON will be ignored.
Axis stop signal
                     [Y4, Y5, Y6, Y7]
OFF
ON
OFF
ON
Forward run JOG start signal
                     [Y8, YA, YC, YE]
QD75 READY signal        [X0]  
PLC READY signal          [Y0]
OFF
ON
Fig. 11.7 Operation when the stop signal is turned ON during JOG operation