12 - 39 
MELSEC-Q
12   CONTROL SUB FUNCTIONS 
 
12.4.4 Hardware stroke limit function 
 
!
WARNING 
When the hardware stroke limit is required to be wired, ensure to wire it in the negative logic using b-contact.   
If it is set in positive logic using a-contact, a serious accident may occur.   
 
In the "hardware stroke limit function", limit switches are set at the upper/lower limit of 
the physical moveable range, and the control is stopped (by deceleration stop) by the 
input of a signal from the limit switch. Damage to the machine can be prevented by 
stopping the control before the upper/lower limit of the physical moveable range is 
reached.  
Hardware stroke limit switches are normally "installed inside the stroke limit/stroke end 
on the drive unit side", and the control is stopped before the stroke limit/stoke end on 
the drive unit side is reached.   
 
The details shown below explain about the "hardware stroke limit function".   
  [1] Control details 
    [2] Wiring the hardware stroke limit   
  [3] Control Precautions 
    [4] When the hardware stroke limit is not used 
 
[1]   Control details 
The following drawing shows the operation of the hardware stroke limit function.   
 
Mechanical stopper
Mechanical stopper
QD75
Movement 
direction
Movement 
direction
QD75 control moveable range
Start
Start
Drive unit
stroke limit
Lower limit
Upper limit
Deceleration stop at
upper limit switch 
detection
Deceleration stop at
lower limit switch 
detection
Lower limit switch
Upper limit switch
Drive unit
stroke limit
Drive unit
 
Fig. 12.22 Hardware stroke limit function operation