15 - 2 
MELSEC-Q
15   TROUBLESHOOTING 
 
15.1 Troubleshooting 
 
(1)  Troubleshooting using the LEDs 
Check items and corrective actions for troubleshooting using the indicator LEDs 
of the QD75 are described below. 
 
(a)      When the RUN LED turns off 
 
Check item 
Action 
Is the power supplied? 
Check that the voltage supplied to the power supply module 
is within the rated range. 
Is the power supply 
capacity sufficient? 
Calculate the total current consumption of the connected 
modules (CPU module, I/O modules, and intelligent function 
modules) and check that the power supply capacity is not 
insufficient. 
Is the module connected 
correctly? 
Check that the module is correctly connected to the base 
unit. 
 
If there is no problem on the above check items, a watchdog timer error 
may have occurred. Reset the CPU module and check that the RUN LED 
turns on. 
If not, the possible cause is a hardware failure. Please consult your local 
Mitsubishi representative. 
 
(b)      When the ERR. LED turns on 
 
Check item 
Action 
Is there a system error? 
An error may have occurred in the CPU module. Check the 
error and take a corrective action. 
 
(c)      When the ERR. LED and axis LED flash 
 
Check item 
Action 
Is there an axis error? 
Check the error code and take the action described in 
Section 15.3. 
 
(d)      When all LEDs turn on 
Reset the CPU module and check that the module is in the normal status. 
If all LEDs still turn on, the possible cause is a hardware failure. Please 
consult your local Mitsubishi representative.