Справочник Пользователя для Mitsubishi Electronics QD75D2N

Скачать
Страница из 860
 
 
 
3 - 16 
MELSEC-Q
3   SPECIFICATIONS AND FUNCTIONS 
 
3.3    Specifications of input/output signals with CPU module 
3.3.1 List of input/output signals with CPU module 
The QD75 uses 32 input points and 32 output points for exchanging data with the CPU 
module. 
The input/output signals when the QD75 is mounted in slot No. 0 of the main base unit 
are shown below. 
Device X refers to the signals input from the QD75 to the CPU module, and device Y 
refers to the signals output from the CPU module to the QD75. 
 
Signal direction: QD75 
  CPU module 
Signal direction: CPU module 
 QD75 
Device No. 
Signal name 
Device No.
Signal name 
X0 
QD75 READY 
Y0 
PLC READY 
X1 Synchronization 
flag Y1 
Use prohibited 
X2 
Use prohibited 
Y2 
X3 Y3 
X4 Axis 
M code ON 
Y4 Axis 
Axis stop 
X5 Axis 
Y5 Axis 
X6 Axis 
Y6 Axis 
X7 Axis 
Y7 Axis 
X8 Axis 
Error detection 
Y8 
Axis 1 
Forward run JOG start 
X9 
Axis 2 
Y9 
Axis 1 
Reverse run JOG start 
XA 
Axis 3 
YA 
Axis 2 
Forward run JOG start 
XB 
Axis 4 
YB 
Axis 2 
Reverse run JOG start 
XC Axis 
BUSY 
YC 
Axis 3 
Forward run JOG start 
XD 
Axis 2 
YD 
Axis 3 
Reverse run JOG start 
XE 
Axis 3 
YE 
Axis 4 
Forward run JOG start 
XF 
Axis 4 
YF 
Axis 4 
Reverse run JOG start 
X10 Axis 
Start complete 
Y10 Axis 
Positioning start 
X11 Axis 
Y11 Axis 
X12 Axis 
Y12 Axis 
X13 Axis 
Y13 Axis 
X14 Axis 
Positioning complete 
Y14 Axis 
Execution prohibition flag
X15 Axis 
Y15 Axis 
X16 Axis 
Y16 Axis 
X17 Axis 
Y17 Axis 
X18 
Use prohibited 
Y18 
Use prohibited 
X19 Y19 
X1A Y1A 
X1B Y1B 
X1C Y1C 
X1D Y1D 
X1E Y1E 
X1F Y1F 
 
Important 
 
[Y1 to Y3], [Y18 to Y1F], [X2, X3], and [X18 to X1F] are used by the system, and cannot be 
used by the user. 
If these devices are used, the operation of the QD75 will not be guaranteed.