6 - 24 
MELSEC-Q
6      SEQUENCE PROGRAM USED FOR POSITIONING CONTROL 
 
6.5 Program details 
6.5.1 Initialization program 
[1]   OPR request OFF program 
This program forcibly turns OFF the "OPR request flag" ( Md.31   Status : b3) 
which is ON. 
When using a system that does not require OPR, assemble the program to 
cancel the "OPR request" made by the QD75 when the power is turned ON, etc. 
 
  Data requiring setting 
 
Set the following data to use the OPR request flag OFF request. 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address 
Axis 1  Axis 2  Axis 3 Axis 4
 Cd.19  
OPR request flag OFF 
request 
Set to "1: Turn OPR request flag OFF". 
1521  1621  1721 1821
 
                                    Refer to Section 5.7 "List of control data" for details on the setting details. 
 
  Time chart for OPR request OFF 
 
OFF
ON
OFF
0
1
0
ON
OFF 
PLC READY signal
 [Y0]
QD75 READY signal 
[X0]
OPR request OFF flag
[  Md. 31 Status: b3]
Cd. 19 OPR request flag OFF request
ON
 
 
Fig. 6.1 Time chart for OPR request OFF 
 
[2]      External command function valid setting program 
This program is used to validate the "external command signal" beforehand when 
using the external command functions (external start, speed change, speed-
position switching, position-speed switching, skip). (Set which function to use 
beforehand in "   Pr.42   External command function selection".) 
Set the following data to validate the "external command signal". 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address 
Axis 1  Axis 2  Axis 3 Axis 4
 Cd.8   External command valid 
Set to "1: Validate external command". 
1505  1605  1705 1805
 
  Refer to Section 5.7 "List of control data" for details on the setting details.