EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
19
74-2958—1
Outdoor Air Humidity (W7750B,C 
only):
Type: Voltage/Current.
Supported Sensors: C7600B1000 and C7600B1018 
(2 to 10V), C7600C1008 (4 to 20mA).
Return Air Humidity (W7750B,C 
only):
Type: Voltage/Current.
Supported Sensors: C7600B1000 and C7600B1018 
(2 to 10V), C7600C1008 (4 to 20mA).
Outdoor Air Enthalpy (W7750B,C 
only):
Type: Current.
Supported Sensors: C7400A1004 (4 to 20mA).
Return Air Enthalpy (W7750B,C 
only):
Type: Current.
Supported Sensors: C7400A1004 (4 to 20mA).
Air Filter Differential Pressure (W7750B,C 
only):
Type: Voltage.
Supported Sensors: Third party 2 to 10V, 0 to 5 inw 
(1.25 kPa) differential pressure sensors.
CO
2
 Sensor (W7750B,C only):
Type: Voltage.
Supported Sensors: Third party 0 to 10V, 0 to 2000 ppm 
CO
2
 sensors.
Monitor Sensor for network use (W7750B,C 
only):
Type: Voltage.
Supported Sensors: Third party 2 to 10V, 2 to 10 volts 
displayed.
DIGITAL INPUTS:
NOTE:
Only one of each type of input is allowed. For 
example, only one Smoke Monitor is allowed. No 
duplicate Smoke Monitors are usable on the same 
controller.
Dry-contact inputs are sensed using a 9 milliamp at 4.8 volts 
detection circuit. It is very important that the device used 
contains high quality, noncorroding contacts with resistivity 
that does not degrade; that is, increase over time. Use noble 
metal (such as gold or silver), or pimpled or sealed contacts to 
assure consistent, long-term operation.
Two of the following Digital Inputs (DIs) can be configured 
when using the W7750A, and four of the following when using 
the W7750B,C:
— Fan Status:
Contact Closed = Fan on
— IAQ Switch:
Contact Closed = Poor Air Quality
— Time Clock:
Contact Closed = Occupied Mode; Contact Open = 
Unoccupied Mode
— Schedule Master:
Contact Closed = Local time clock is used as master time 
clock
— Economizer Enable Signal:
Contact Closed = Economizer Enabled for cooling use
— Smoke Monitor:
Contact Closed = Smoke Detected
— Dirty Filter:
Contact Closed = Dirty Filter
— Shutdown Signal:
Contact Closed = Shut off all equipment
— Occupancy Switch:
Contact Closed = Room is Occupied; Contact Open = 
Room is Unoccupied
— Window Monitor:
Contact Closed = Window is Closed
— Coil Freeze Stat: (Only use this DI when using E-Vision.)
Contact Closed = Coil Freeze condition sensed
— Wall Module Bypass Pushbutton:
Momentary DI (See Appendix B—Sequences of Operation 
for bypass details.)
TRIAC OUTPUTS ON THE (W7750B,C MODELS ONLY):
— Power ratings: 20 Vac to 30 Vac at 25 mA MIN to 500 mA 
MAX current for any voltage.
CAUTION
When any device is energized by a Triac, the device 
must be able to sink a minimum of 25 mA.
NOTE:
Triacs sink current to the 24 Vac common (COM 
terminal on the W7750B,C Models); see Fig. 30 for 
wiring example.
IMPORTANT
If non-Honeywell motors, actuators, or transducers 
are to be used with Excel 10 Controllers, Triac com-
patibility must be verified (see previous NOTE).
DIGITAL OUTPUTS:
COOL STAGE 1
COOL STAGE 2
COOL STAGE 3
COOL STAGE 4
HEAT STAGE 1
HEAT STAGE 2
HEAT STAGE 3
HEAT STAGE 4
CHANGE OVER RELAY
FAN
AUX ECON
OCCUPANCY STATUS
ECON OPEN
ECON CLOSE
COOL OPEN
COOL CLOSE
HEAT OPEN
HEAT CLOSE
HEAT COOL STAGE 1
HEAT COOL STAGE 2
HEAT COOL STAGE 3
HEAT COOL STAGE 4
FREE1 (NOTE: Free1, Free1 Pulse On and Free1 Pulse Off 
are three separate and unique digital output points. Because 
they are not related, they all can be configured in a CVAHU 
controller at the same time.)
FREE2
FREE1 PULSE ON
FREE1 PULSE OFF
ECON PWM
HEAT PWM
COOL PWM
UNUSED