EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
22
Configurations
General
Tables 3 and 4 provide an overview of the Excel 10 W7750 
configuration options. All W7750s are assumed to have a 
supply fan digital output. Additionally, Tables 3 and 4 list the 
general mechanical equipment options available with the 
W7750 Controller. See Application Step 6. Configure 
Controllers, for further information on configurations.
CAUTION
For floating control, the Excel 10 W7750 Controller is 
designed to work only with Series 60 valve and 
damper actuators. Full stroke actuator drive-time must 
be between 20 and 240 seconds (0.25 to 4.0 minutes).
Table 3. Common Configuration Options Summary For W7750A,B,C Controllers.
Option
Possible Configurations Common To All W7750 Models
Supply Fan 
1. Mandatory Digital Output.
Type of Air Handler
1. Conventional.
2. Heat Pump.
Occupancy Sensor
1. None.
2. Connected: Contacts closed equals Occupied.
3. Network (Occ/Unocc signal received via the L
ON
W
ORKS
 Bus network).
Window Sensor
1. None.
2. Physically Connected: Contacts closed equals window closed.
3. Network (Window Open/Closed signal received via the L
ON
W
ORKS
 Bus).
Wall Module Option
1. Local (direct wired to the controller).
(The T77560A,B has no L
ON
W
ORKS
 Bus access)
2. Network (sensor value received via the L
ON
W
ORKS
 Bus).
Wall Module Type
1. Sensor only.
(All wall modules have a L
ON
W
ORKS
 Bus access 
2. Sensor and Setpoint adjust.
jack except T7560A,B)
3. Sensor, Setpoint adjust and Bypass.
4. Sensor and Bypass.
Smoke Emergency Initiation
1. None.
2. Physically Connected: Contacts closed equals smoke detected.
3. Network (Emergency/Normal signal received via the L
ON
W
ORKS
 Bus).