EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
25
74-2958—1
Fig. 15. Heat pump with two compressors and auxiliary 
heat stage(s).
ECONOMIZER CONTROL
Economizer control is available concurrently with any 
configuration in the W7750 when DOs are not all used by the 
heating and cooling equipment. Two types of economizer 
controls are supported by the W7750 Controller, modulating 
control and enable/disable control. Modulating control can be 
either Series 60 Floating Control or PWM control (PWM 
control is available on the W7750B,C only). A discharge air 
temperature sensor is required for modulating economizer 
damper control. Enable/disable control is provided to emulate 
the Honeywell T7300 thermostat economizer operation, 
where a DO tracks the occupancy status of the controller. An 
external packaged economizer control then modulates the 
dampers. For modulating control, the economizer is enabled 
or disabled based on one of ten available strategies (see 
Appendix B—Sequences of Operation—Economizer Enable/
Disable Control section, for further details). Fig. 16 illustrates 
a system with modulating economizer dampers (see Fig. 29, 
31, 32 and 35 in Step 4. Prepare Wiring Diagrams section, for 
wiring details).
Fig. 16. Economizer control.
PNEUMATIC ACTUATOR CONTROL
The W7750B,C Controller can control pneumatic actuators for 
any or all of the three modulating outputs provided by the 
control algorithm (heat, cool and economizer). Control of 
pneumatic water/steam valves and damper actuators is 
provided through a transducer device using either Series 60 
Floating Control or PWM DOs. A floating-to-pneumatic, or a 
PWM-to-pneumatic transducer is required for each output 
signal. The W7750A Controller can drive Series 60 Floating 
Control to modulate cooling valves, heating valves and 
economizers. There are no PWM outputs configurable on the 
W7750A model.
For projects with existing pneumatically actuated reheat 
valves, the Excel 10 W7750 Controller output must be 
converted to a pneumatic signal using a transducer device 
developed for use with Excel 10 Controllers. The transducer is 
MIXED
AIR
AUXILIARY
HEAT
STAGE(S)
SHARED 
HEAT AND
COOL COIL
DISCHARGE
AIR
+
FAN
FAN
STARTER
COMPRESSOR AND
CHANGEOVER VALVE
COMP 1
COMP 2
CHANGEOVER 
RELAY
M17493
EXCEL 10
CVAHU
W7750A,B,C
T7560A,B OR T7770
OUTDOOR
AIR
RETURN
AIR
HEAT
COIL
COOL
COIL
DISCHARGE
AIR
-
+
FAN
FAN
STARTER
DISCHARGE
TEMPERATURE
SENSOR REQUIRED
FOR ECONOMIZER
CONTROL
M
PWM OR
SERIES 60
FLOATING
MOTOR
M17494
EXCEL 10
CVAHU
W7750A,B,C
T7560A,B OR T7770