Справочник Пользователя для Honeywell W7750A

Скачать
Страница из 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
62
INDOOR AIR QUALITY (IAQ) OVERRIDE
The Excel 10 W7750 Controller supports an IAQ override 
feature that upon detection of poor air quality in the space, 
allows the economizer dampers to be opened above the 
standard minimum position setting to a value set in 
EconIAQPos. Two different methods of detecting poor air 
quality are supported, The first is by using an IAQ switch 
device connected to a digital input on the W7750 Controller, 
where a contact closure indicates poor air quality and initiates 
the IAQ override mode. The second, which is only available 
on the W7750B,C is through an analog input that connects to 
a CO
2
 Sensor (0 to 10V). The measured value of CO
2
 from 
this sensor (0 to 2000 ppm) is compared to the setpoint 
IAQSetpt. When the CO
2
 level is higher than the setpoint (800 
PPM), the IAQ override is initiated. The IAQSetpt hysteresis is 
50 PPM, IAQ override is deactivated at a CO
2
 level less than 
750 PPM.
When the W7750 Controller is in the COOL mode during an 
IAQ override, it is possible for the heating outputs to be 
activated. This can occur if the outdoor air temperature is cold 
enough to cause the discharge air temperature to drop below 
the DaTempLoLim setpoint when the dampers open to the 
EconIAQPos position, and the IaqUseHeat flag is set. If this 
situation occurs, the heating is controlled to maintain the 
discharge air temperature at 1°F (0.65°C) above the 
DaTempLoLim setpoint.
FREEZE STAT
Upon receiving a contact closure, the W7750 control 
algorithm will close the outdoor air damper and open the hot 
water and chilled water valves (if available) to the full open 
position as a safety precaution. If manual-reset operation is 
desired, the Freeze Stat device must provide the physical 
pushbutton, which the operator presses, to reset the system 
after a freeze condition has occurred.
DISCHARGE AIR LOW LIMIT CONTROL
If the discharge air temperature falls below the user-settable 
discharge air low limit setpoint (DaTempLoLim), an alarm is 
issued, and the outdoor air damper is driven below the 
minimum position setting until the discharge temperature is up 
to the low limit. If necessary, the damper can go completely 
closed even during Occupied mode operation. As the 
discharge temperature warms up, the economizer modulates 
open until the minimum position setting is reached. At this 
point, the low limit alarm is cleared.
ECONOMIZER ENABLE/DISABLE CONTROL
The W7750 Controller has inputs to determine if the outdoor 
air is suitable to augment cooling. The economizer dampers 
can be enabled/disabled for using outdoor air as the first 
stage of cooling based on one of ten allowable strategies:
1.
Digital Input Enable/Disable—contact closure enables 
economizer.
2.
Outdoor Temperature—when the outdoor temperature 
is less than OaEconEnTemp, then the outdoor air is 
suitable to augment cooling.
3.
Outdoor Enthalpy, Type A—when the outdoor 
enthalpy meets the H205 type A requirements, the 
outdoor air is suitable to augment cooling.
4.
Outdoor Enthalpy, Type B—when the outdoor 
enthalpy meets the H205 type B requirements, the 
outdoor air is suitable to augment cooling.
5.
Outdoor Enthalpy, Type C—when the outdoor 
enthalpy meets the H205 type C requirements, the 
outdoor air is suitable to augment cooling.
6.
Outdoor Enthalpy, Type D—when the outdoor 
enthalpy meets the H205 type D requirements, the 
outdoor air is suitable to augment cooling.
7.
Differential Temperature—the difference between 
outdoor temperature and return air temperature is 
compared to DiffEconEnTemp to determine whether 
outdoor air or return air is more suitable for use to 
augment mechanical cooling.
8.
Single Calculated Enthalpy—the calculated outdoor 
enthalpy in btu/lb is compared to the enthalpy setpoint 
(OaEnthEn) in btu/lb, and the outdoor temperature is 
compared to the outdoor temperature limit setpoint 
(OaEconEnTemp) for a high limit. The compared 
difference determines whether outdoor air is suitable for 
use to augment mechanical cooling.
9.
Differential Enthalpy, Either Sensed or Calculated—
the difference between outdoor enthalpy and return air 
enthalpy determines whether outdoor air or return air is 
more suitable to augment mechanical cooling. When 
enthalpy sensors are configured, they are used for 
comparing enthalpy. If no enthalpy sensors are 
available, then enthalpy is calculated using outdoor and 
return air humidity and temperature sensors. The 
switching differential is fixed at 1.0 mA for enthalpy 
sensors, and 0.25 btu/lb for calculated enthalpy.
NOTE:
If no return temperature sensor is configured, 
space temperature is used to calculate return 
air enthalpy.
10.
Network Enabled—the network input DestEconEnable 
controls the enabling and disabling of the economizer. 
When using the network input, select Econo Enable 
Type: No Economizer in E-Vision. The network input 
has priority over the other nine economizer control 
selections.
Appendix C. Complete List of Excel 10 
W7750 Controller User Addresses.
See Table 18 for W7750 Controller User Address table 
numbers and point types.
The User Address Index following Table 18 lists the User 
Addresses alphabetically and gives the page number where 
the Address is located in each Table Number/Point Type.
After Table 18 there is an alphabetical list of Mappable User 
Addresses and Table Numbers. Following this is an 
alphabetical list of Failure Detect User Addresses and Table 
Numbers.
Table 18. Excel 10 W7750 Controller User 
Address Point Types.
Table Number
Point Types
Table 20
Input/Output
Table 21
Control Parameters
Table 22
Energy Management Points
Table 23
Status Points
Table 24
Calibration Points
Table 25
Configuration Parameters
Table 26
L
ON
M
ARK
/Open System Points
Table 27
Direct Access and Special Manual Points
Table 28
Data Share Points