10 Troubleshooting
10.1 Troubleshooting procedure
101
FX
3U
-CF-ADP User's Manual
1
Introduc
tion
2
S
pecifi
cation
3
Sy
stem
 
Configurati
o
n
4
Ins
tal
lation
5
Wi
rin
g
6
Functi
o
n
s
7
Bef
o
re
 
Programm
ing
8
C
F
-AD
P
 Appl
ied 
Ins
tructi
ons
 
Explanati
o
n
9
Program 
Examples
10
T
roubl
esho
oti
n
g
10.1
Troubleshooting procedure
10.1.1
LED status check
The table below describes details for LED statuses.
10.1.2
Troubleshooting by error code
When an error occurs, the PLC turns ON the special auxiliary relay M8329 (instruction execution abnormal
end), and aborts execution of the instruction. After that, the PLC stores error codes in the special data register
for error code storage, and turns ON the error flag.
1. Checking the error status by monitoring special data registers
Monitor the special data registers shown below to check the error code, error code details and step number
where the error has occurred.
→ For details of error codes, refer to Subsection 10.1.3.
2. Checking the error status by executing the FLSTRD instruction
Execute the FLSTRD instruction (FNC305 for the CF-ADP) to check the error code of the 5 latest errors.
→ For details of the instruction, refer to Chapter 8.
→ For details of error codes, refer to Subsection 10.1.3.
LED 
display
Color
Status
Description
Error corrective action
POWER
Green
OFF
Power is not being supplied from the external
power supply (24V DC).
Correctly connect the power cable.
Correctly connect the wiring to the external
power supply.
When the service power supply of the PLC
main  unit  is  in  use,  make  sure  that  the  supply
capacity is not being exceeded.
ON
Power is being supplied from the external power
supply (24V DC).
The power supply is normal.
BUFFER
Green
OFF
Data is not stored in the internal buffer.
-
ON
Data is stored in the internal buffer.
-
ERR.
Red
OFF
No errors.
-
ON
CF write error, CompactFlash
TM
 card error, etc.
has occurred.
An error has occurred in the CF-ADP.
Check the error code, and perform the appropriate
action according to the content of the error.
For details on error codes, refer to the following.
→ Refer to Subsection
10.1.3
FULL
Red
OFF
The CompactFlash
TM
 card has free space.
-
Flicker
The free space in the CompactFlash
TM
  card  is  at
20% or less of the full capacity.
-
ON
The CompactFlash
TM
 card has no free space.
The free space in the CompactFlash
TM
  card  is  at
1% or less of the full capacity.
Delete unnecessary data, or replace the
CompactFlash
TM
 card.
ACCESS
Red
OFF
CompactFlash
TM
 card not accessed
-
ON
CompactFlash
TM
 card being accessed
-
SLOT
Green
OFF
The CompactFlash
TM
 card is not inserted, or the
slot is in the CompactFlash
TM
 card unmounted
status.
The CompactFlash
TM
 card is not inserted
Insert a CompactFlash
TM
 card.
ON
The CompactFlash
TM
 card is inserted, or the slot is
in the card mounted status.
-
Error code storage device
Error code detail storage device
Error detected step number storage 
device
ch1
ch2
ch1
ch2
ch1
ch2
D8418
D8438
D8417
D8437
D8415,D8414
D8435,D8434