5 Wiring
5.2 Power Supply Wiring
30
FX
3U
-CF-ADP User's Manual
5.2
Power Supply Wiring
5.2.1
Power supply wiring
*1.
The expansion board is required when connecting with the FX
3UC
-32MT-LT PLC.
Power-on/off timing
The CF-ADP power supply should be turned ON simultaneously with or before the power supply of the PLC 
main unit. Before turning the power OFF, ensure the safety of the system and then simultaneously turn the 
main unit, CF-ADP, and other extension equipment (the special extension equipment is included) OFF.
For details, refer to the respective PLC manual.
→ Refer to the FX
3U
 Hardware Edition
→ Refer to the FX
3UC
 Hardware Edition
5.3
Grounding
Ground the cables as follows
• The grounding resistance should be 100  or less.
• Independent grounding should be established whenever possible.
Independent grounding should be performed for best results.
When independent grounding is not configured, perform "shared grounding" as shown in the following 
figure.
For details, refer to the respective PLC manual.
→ Refer to the FX
3U
 Hardware Edition
→ Refer to the FX
3UC
 Hardware Edition
• The grounding point should be close to the CF-ADP, and all grounding wires should be as short as 
possible.
Grounding
FX
3U 
PLC
[Main unit]
CF-ADP
24+
24-
Grounding
Stabilized
power supply
24V DC
Power connector
Green
Red
Black
Expansion 
board
FX
3UC
 PLC
[Main unit]
Grounding
CF-ADP
24+
24-
Grounding
Stabilized
power supply
24V DC
Power connector
Green
Red
Black
Expansion 
board
*1
CF-ADP
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
CF-ADP
Other
equipment
CF-ADP
Other
equipment