Programming Manual - Basic & Applied Instruction Edition
13 High-Speed Processing – FNC 50 to FNC 59
13.4 FNC 53 – HSCS / High-Speed Counter Set
11
FN
C30
-FN
C3
9
R
ota
tion and 
Shi
ft
12
FN
C40-FN
C49
D
ata O
perati
on
13
FNC
50-FNC
59
High-Speed
 
Proc
essing
14
FM
C60-FN
C69
H
andy 
In
struction
15
FN
C70-FN
C79
E
xternal
 F
X
 I/O
 
De
vice
16
FNC
80-FNC
89
External
 FX 
Dev
ice
17
FNC1
00-
FNC10
9
Dat
Transfer 2
18
FNC1
10-
FNC139
Fl
oati
ng Poi
nt
19
FNC14
0-F
N
C
149
Da
ta
 
Operation 2
20
FNC1
50-
FNC159
Pos
itioning 
Control
Operation
When the current value of the high-speed counter C255 changes from "99" to "100" or from "101" to "100", Y010 is set
to ON (output refresh).
Related instructions
The following instructions can be combined with high-speed counters:
Cautions
1. Selection of the count comparison method
1) FX
3U
/FX
3UC
 PLC
When the HSCS instruction is used in FX
3U
/FX
3UC
 PLCs, hardware counters (C235, C236, C237, C238, C239,
C240, C244 (OP), C245 (OP), C246, C248 (OP), C251 and C253) are automatically switched to software
counters, and the maximum frequency and total frequency of each counter are affected.
Refer to the counting operation described below, and select according to the contents of control whether to use
HSCS instruction or general-purpose comparison instruction.
a) Case to select DHSCS instruction
-
When the output should be given when the counting result becomes equivalent to the comparison value
regardless of the scan time of the PLC
b) Cases to select a general-purpose comparison instruction
-
When the frequency is beyond the counting performance of software counters (and below the counting
performance of hardware counters)
-
When counting is regarded as important, but the effect of the scan time can be ignored in operations
according to the counting result
-
When one instruction is executed in 33 or more positions at the same time
Instruction
FNC No.
Instruction name
DHSCS
FNC 53
High-speed counter set
DHSCR
FNC 54
High-speed counter reset
DHSZ
FNC 55
High-speed counter zone compare
DHCMOV
FNC189
High-speed counter move
DHSCT
FNC280
High-speed counter compare with data table
M8000
RUN monitor
C255
K2,147,483,647
FNC 53
DHSCS
K100
C255
Y010
=
K100
C255
Y010
Set to ON.
Comparison
value
Comparison
source
Output
destination
M8000
FNC189
DHCMOV
C251
D100
K0
SET
Y010
FNC229
LDD<=
K100
D100
FNC 50
REF
Y010
K8