9 - 58 
MELSEC-A
9   MAIN POSITIONING CONTROL 
 
(2)   Current value change using the start No. (No. 9003) for a current 
value change 
 
 Operation chart 
 
The current value is changed by setting the new current value "Current value 
change (RWwm+2 to 3, RWwm+10 to 11)", setting "9003" in the "
Cd.11  
Positioning start No.", and turning ON the positioning start signal. 
 
                                                     
Positioning  start signal
Current feed value
50000
0
OFF
ON
Current value changes to the 
positioning address designated by
the new current value remote register.
The above chart shows an example
when the positioning address is "0".
[RY(n+1)0, RY(n+1)1]
[RWrn+0 to 1, RWrn+8 to 9]
 
 
 Restrictions 
 
(1)  An error "Outside current value change range" (error code: 514) will occur if 
the designated value is outside the setting range when "degree" is set in 
" Pr.1  Unit setting". 
 
(2)  An error will not occur even if the designated value is outside the software 
stroke limit range.  
However, an error "Start outside stroke limit +/-" (error code: 507/508) will 
occur at the positioning start.  
 
(3)  The current value cannot be changed during stop commands and while the M 
code ON signal is ON.  
 
 Current value change procedure 
 
The following shows the procedure for changing the current value to a new value.  
 
Turn ON the positioning start signal. 
(RY(n+1)0, RY(n+1)1)
Write "9003" in "Positioning start No."
(RWwm, RWwm+8)
1)
2)
3)
 Write the current value to "New current value
(RWwm+2 to 3, RWwm+10 to 11)"