1 - 16 
MELSEC-A
1   PRODUCT OUTLINE 
 
1.2.3 Outline of stopping 
Each control is stopped in the following cases. 
 
(1)  When each control is completed normally. 
(2)  When the drive unit READY signal is turned OFF. 
(3)  When the data link of CC-Link stops. 
(4)  When Initial data setting request (RY(n+7)9) turns ON and Remote station READY 
(RX(n+7)B) turns OFF. 
(5)  When an error occurs in the D75P2. 
(6)  When control is intentionally stopped (Stop signal from master module turned ON, 
stop from peripheral device, etc.) 
 
The outline for the stopping process in these cases is shown below. (Excluding (1) for 
normal stopping.) 
 
Stop cause 
Stop 
axis 
Axis 
operation 
status after 
stopping 
(RWrn+7, 
RWrn+15)
Stop process 
Zero point return 
control 
Main 
positioning 
control 
Advanced 
positioning 
control 
Manual control 
Machine 
zero point 
return 
control 
High-
speed 
zero 
point 
return 
control
JOG 
opera-
tion 
Manual 
pulse 
generator 
operation 
Forced stop 
Drive unit 
READY signal 
OFF 
Each 
axis 
During 
error 
 Immediate 
stop 
Immediate 
stop 
Fatal stop 
(Stop group 1) 
Hardware stroke 
limit upper/lower 
limit error 
occurrence 
Each 
axis 
During 
error 
 Deceleration 
stop/sudden 
stop 
 
 (Select with 
Pr.38  ) 
Decelera-
tion stop 
Emergency 
stop  
(Stop group 2) 
Software stroke 
limit upper/lower 
limit error 
occurrence 
Each 
axis 
During 
error 
 Deceleration 
stop/sudden 
stop 
 
 (Select with  Pr.39  ) 
Decelera-
tion stop 
Remote station 
READY signal 
OFF 
All 
axes 
"Stop" input from 
peripheral device 
Relatively safe 
stop  
(Stop group 3) 
Axis error 
detection (Error 
other than stop 
group 1 or 2) 
Each 
axis 
During 
error 
 Deceleration 
stop/sudden 
stop 
 
 (Select with  Pr.40  ) 
Decelera-
tion stop 
Error in test 
mode 
Intentional stop 
(Stop group 3) 
"Stop signal" ON 
from external 
source 
Each 
axis 
When 
stopped 
(While 
waiting) 
"Axis stop signal" 
ON from PLC 
CPU