12 - 39 
MELSEC-A
12   CONTROL AUXILIARY FUNCTIONS 
 
(4)   Setting the speed change function using an external start signal 
The speed can also be changed using an "external start signal".  
The following shows the data settings for changing the control speed of axis 1 
using an "external start signal". (In this example, the control speed is changed to 
"20.00mm/min".) 
 
(a)  Set the following data to change the speed using an external start signal. 
(Use the start time chart shown in section (2) below as a reference, and set 
using the sequence program shown in section (3).) 
 
Setting item 
Setting 
value 
Setting details 
Remote input/output, 
remote register, buffer 
memory address 
Axis 1 
Axis 2 
Pr.43  
External start 
function selection 
Set "1: External speed change request". 
62 
212 
New speed value 
2000  Set the new speed. 
RWwm+4 
RWwm+5 
RWwm+12
RWwm+13
External start valid 
ON 
Set "ON: Validate the external start". 
RY(n+2)B  RY(n+4)B
 
                 * Refer to section "3.4 Specifications of input/output signals for master module", "3.5 Remote registers" and  
                   "5.2 List of parameters" for details on the setting details. 
 
(b)  The following shows the speed change time chart. 
 
Pr.43  External start function selection 
New speed value 
V
t
2000
1
In speed change processing flag
External start valid
Dwell time
BUSY signal
Error detection signal
Remote station READY 
signal
Positioning start signal
Positioning complete signal
D75P2 READY signal
Start complete signal
[RY(n+1)0]
[RXn4]
[RXn0]
[RX(n+7)B]
[RXn1]
[RXnA]
[RXn7]
External start signal 
[RX(n+1)1, RX(n+4)1]
[RWwm+4 to 5, RWwm+12 to 13]
[RY(n+2)B, RY(n+4)B]
Fig. 12.26 Time chart for changing the speed using an external start signal